# 2\-wires, 3\-wires, preset I/Os assignment

[Home](/articles/clean-power-vfd-publication/home) » [Functions and parameters](/articles/clean-power-vfd-publication/folder-functions-and-parameters) » [Inputs and outputs](/articles/clean-power-vfd-publication/i-o) » [I/O's preset configuration](/articles/clean-power-vfd-publication/inputs-and-outputs-preset-configuration) » 2-wires, 3-wires, preset I/Os assignment

* * *
 
The following sections explain the two primary methods for wiring the VFD control inputs and outputs, commonly referred to as **2-wire** and **3-wire** configurations.

These two options provide flexibility in how the VFD is controlled, whether using a maintained contact, such as a PLC output, or separate momentary pushbuttons, such as a dedicated Start/Stop station.

The following sections describe each control mode, the default I/O assignments, and their operation.

* * *

![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Yellow%20Caution.png)

> 
> **IMPORTANT — CONTROL SOURCE**
> 
> The Start, Stop, and Direction commands assigned to the digital inputs are control commands from the **digital I/O control source**.
> 
> These commands control the motor only when the corresponding I/O source is the active control source.
> 
> For example, if the VFD is operating in **Local** control, a Start or Stop command received from a digital input does not control the motor. This is particularly important in **3-wire control**, where a physically wired Stop pushbutton does **not** stop the motor while Local control is active.
> 
> Refer to **[Control Source](/articles/clean-power-vfd-publication/control-source)** for information about Local and Remote control-source selection.

> 
> **NOT A SAFETY FUNCTION**
> 
> The Start and Stop commands described in this topic are operational control functions. They do not replace an emergency-stop circuit, Safe Torque Off (STO), or an energy-isolation procedure.

* * *

## 2-wire, 3-wire, preset I/O assignment

There are 2 wiring presets with their configuration selectable by the user, via the mobile application:

* 2-wires mode
* 3-wires mode.

“2-wire” and “3-wire” refer to two different ways you can wire the start/stop control (and sometimes forward/reverse) inputs for the drive.

* **2-wire control** is typically used with maintained contacts, such as PLC outputs or selector switches.
* **3-wire control** is typically used with separate momentary Start and Stop pushbuttons.

The preset configuration is editable by the user during the configuration phase of the VFD.

The default preset is the 3-wire configuration.

The following drawings show the I/O's that are used in the default presets with their function assignment. Those drawings are not wiring diagrams.

* Check the [standard connection diagram](/articles/clean-power-vfd-publication/standard-connection-diagram) section for the wiring.
* Check the [control circuit description](/articles/clean-power-vfd-publication/control-circuit-description) section for the attributes and values of the control terminals,
* and check the [digital input logic connection](/articles/clean-power-vfd-publication/digital-input-logic-connection) section for the details of Source and Sink logic connection modes.

Wiring presets are available for speed control mode and torque control mode, with some slight differences in I/O assignment.

| I/O | 2- wires preset | 2- wires preset | 3-wires preset | 3-wires preset |
| --- | --- | --- | --- | --- |
|  | **Speed control** | **Torque control** | **Speed control** | **Torque control** |
| Di 3 | run forward | torque applied in the forward direction | run forward | torque applied in the forward direction |
| Di 4 | run reverse | torque applied in the reverse direction | run reverse | torque applied in the reverse direction |
| Di5 |  |  | stop | stop |
| Di 6 | select speed reference ([if a preset speed is defined](/articles/clean-power-vfd-publication/preset-speeds)) |  | select speed reference ([if a preset speed is defined](/articles/clean-power-vfd-publication/preset-speeds)) |  |
| Ai 1 | speed setpoint |  | speed setpoint |  |
| Ai 2 |  | torque setpoint |  | torque setpoint |
| Relay 1 | alarm output | alarm output | alarm output | alarm output |
| Relay 2 | ready to run | ready to run | ready to run | ready to run |
| Relay 3 | running | running | running | running |
| Aq 1 | motor speed | motor torque | motor speed | motor torque |
| Aq 2 | motor current | motor current |  |  |

**2-wires connection for speed control:**

![](/resources/Storage/clean-power-vfd-publication/res/2Wires-control_v2.png)

**3-wires connection for speed control :**

![](/resources/Storage/clean-power-vfd-publication/res/3Wires-control_v2.png)

**2-wires connection for torque control:**

![](/resources/Storage/clean-power-vfd-publication/Wiring%20preset%20torque%20mode%202-wire.png)

**3-wires connection for torque control :**

![](/resources/Storage/clean-power-vfd-publication/Wiring%20preset%20torque%20mode%203-wire.png)

For operation, read the chapters:
[3-wires preset- Operation](/articles/clean-power-vfd-publication/3-wires-control-mode)

and

[2-wires preset- Operation](/articles/clean-power-vfd-publication/2-wires-control-mode)