# 3\-wires preset\- Operation 

[Home](/articles/clean-power-vfd-publication/home) » [Functions and parameters](/articles/clean-power-vfd-publication/folder-functions-and-parameters) » [Inputs and outputs](/articles/clean-power-vfd-publication/i-o) » [I/O's preset configuration](/articles/clean-power-vfd-publication/inputs-and-outputs-preset-configuration) » 3-wires preset- Operation

* * *
 
In 3-wires mode, the basic controls are:

* Run forward (default: Di3 input)
* Run reverse (default: Di4 input)
* Stop (default: Di5 input)

Pressing the run forward or the run reverse button momentarily “latches” the drive into a running state internally.

When the **digital I/O control source is active**, pressing the Stop button breaks that latch, causing the drive to stop the motor

The control inputs are managed as pulses of a minimum duration of 20ms.

[Simultaneous activation of run forward and run reverse](/articles/clean-power-vfd-publication/spinning-direction-priority) is managed depending user setting for the priority of spinning direction.

![](/resources/Storage/clean-power-vfd-publication/res/3-wires_time_chart_1.png)

The 3-wire mode can be configured to operate only in the forward direction.

When the single direction is enabled, the preset I/O "Run Reverse" (digital input number 4) is available to be associated with another function such as selecting a preset speed

* * *

![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Orange%20Warning.fr-CA.png)

> 
> **WIRED STOP MAY BE INACTIVE**
> 
> The 3-wire Stop input is associated with the digital I/O control source. It is not an independent or overriding Stop function.
> 
> If the active control source is **Local**, pressing the physical Stop pushbutton connected to DI5 does **not** stop the motor.
> 
> If another Remote control source is active instead of the digital I/O source, such as a network control source, the DI5 Stop command is likewise not used to control the motor.
> 
> Before operating the equipment, verify which control source is active and which Stop command is available.
> 
> 

* * *

## Changing between Local and Remote control

Special attention is required when the control source is changed while the motor is running.

If the VFD is running in **Remote digital I/O control** and the control source is changed to **Local**:

* the motor does not automatically stop;
* control authority moves to the Local control source;
* the 3-wire Start, Stop, and Direction inputs no longer control the motor;
* pressing the wired Stop pushbutton connected to DI5 does not stop the motor;
* use a valid Stop command from the Local control source to stop the motor.

If the control source is changed from **Local** to **Remote digital I/O control** while using 3-wire control, the VFD does not use an already-existing input state as a new command.

A new valid 3-wire input transition is required.

For example, if the Stop input is already active when Remote digital I/O control becomes active, that existing state does not constitute a new Stop command. A new valid Stop action must occur.

## RECOMMENDATION

Avoid changing the active control source while the motor is running.

When a control-source change is required, stop the motor using the currently active control source before changing sources. After the change, verify the active Start and Stop controls before restarting the motor.