# Acceleration and deceleration ramp selection

[Home](/articles/clean-power-vfd-publication/home) » [Functions and parameters](/articles/clean-power-vfd-publication/folder-functions-and-parameters) » [Motor Control Mode](/articles/clean-power-vfd-publication/motor-control-mode) » [General](/articles/clean-power-vfd-publication/general)» [Acceleration and deceleration](/articles/clean-power-vfd-publication/acceleration-and-deceleration) » Acceleration and deceleration ramp selection

* * *
 
The Clean Power VFD allows the user to define **up to 4 acceleration and 4 deceleration ramps**.

With digital inputs, Modbus TCP, BACnet IP, and user-friendly interfaces on both the HMI and mobile app, operators can easily manage and switch between predefined ramps to suit specific motor performance requirements.

The selection of ramps can be achieved through:

* Digital Inputs (DI)
* Modbus TCP
* BACnet IP

**Digital Input (DI) Ramp Selection**

Using a single digital input (DI), the user can switch between two defined acceleration and deceleration ramps.

DI Assignment:

* The mobile app allows the user to assign a digital input for switching both acceleration and deceleration ramps.
* This same digital input is used for switching during both ramp-up and ramp-down phases.

Ramp Switching:

* When the digital input changes from 0 to 1, the VFD will switch from ramp 1 to ramp 2 during both ramp-up and ramp-down.
* When the digital input changes from 1 to 0, the VFD will switch from ramp 2 to ramp 1 during both ramp-up and ramp-down.

**Acceleration Ramp Only Selection**

In this mode, a dedicated digital input can be used to control only the acceleration ramp selection.

DI Assignment:

* The mobile app allows the user to assign a digital input exclusively for switching the acceleration ramp.

Ramp Switching:

* When the digital input changes from 0 to 1, the VFD will switch from acceleration ramp 1 to acceleration ramp 2 during ramp-up.

* When the digital input changes from 1 to 0, the VFD will switch back to acceleration ramp 1 during ramp-up.

**Deceleration Ramp Only Selection**

This mode allows for using a dedicated digital input for selecting only the deceleration ramp.

DI Assignment:

* The mobile app allows the user to assign a digital input exclusively for switching the deceleration ramp.

Ramp Switching:

* When the digital input changes from 0 to 1, the VFD will switch from deceleration ramp 1 to deceleration ramp 2 during ramp-down.
* When the digital input changes from 1 to 0, the VFD will switch back to deceleration ramp 1 during ramp-down.

**Modbus TCP Ramp Selection**

Acceleration Ramp Selection

* The Modbus TCP interface provides a specific register for selecting the acceleration ramp.

Ramp Switching:

* On a Modbus write operation to the acceleration ramp register, the VFD will switch from the current ramp to the specified acceleration ramp (1-4) during ramp-up.

Deceleration Ramp Selection

* A separate register is provided via Modbus TCP for deceleration ramp selection.

Ramp Switching:

* A write operation on the deceleration ramp register will switch the VFD to the selected deceleration ramp (1-4) during ramp-down.

**BACnet IP Ramp Selection**

Acceleration Ramp Selection

* The BACnet IP protocol supports a BACnet MV (Multi-State Value) object for selecting the acceleration ramp.

Ramp Switching:

* When a command/write operation is performed on the acceleration ramp MV object, the VFD will switch from the current ramp to the selected acceleration ramp (1-4) during ramp-up.

Deceleration Ramp Selection

* A separate BACnet MV object is provided for selecting the deceleration ramp.

Ramp Switching:

* A command/write operation on the deceleration ramp MV object will switch the VFD to the selected deceleration ramp (1-4) during ramp-down.

**HMI and Mobile App Ramp Selection**

When more than one ramp is defined for acceleration or deceleration, both the HMI and mobile app display the currently selected ramp during both ramp-up and ramp-down phases.