# Acceleration and deceleration

[Home](/articles/clean-power-vfd-publication/home) » [Functions and parameters](/articles/clean-power-vfd-publication/folder-functions-and-parameters) » [Motor Control Mode](/articles/clean-power-vfd-publication/motor-control-mode) » [General](/articles/clean-power-vfd-publication/general)» Acceleration and deceleration

* * *
 
**Acceleration time**

Acceleration time, also known as **ramp-up time**, defines the duration required for the motor to transition from a standstill to its rated speed.

* **In torque control**, it refers to the time needed for the motor torque to increase from zero to 100% of its rated value.
* The default setting **is 20 seconds**, but this may not suit all applications.
* The acceleration time is adjustable up to **3600 seconds** **.**
* **Caution:**

    Setting the acceleration time too short can result in overcurrent conditions.

**Deceleration time**

Deceleration time, also called **ramp-down time**, controls the time needed for the motor to slow down, typically to a complete stop.

* **In torque control**, it defines the time required for the motor torque to decrease from its rated value to zero.
* The default setting is **20 seconds**, but this can also be adjusted up to **3600 seconds**to fit specific application needs.
* During deceleration, the motor speed exceeds the synchronous speed (corresponding to the Clean Power VFD output frequency), causing the motor to act as a generator. This process, known as

    **regeneration**, results in the motor returning energy to the VFD, causing the DC voltage to increase.

| ![Information](/resources/Storage/clean-power-vfd-publication/info.png) | if the deceleration time is too short it will produce an overvoltage condition |
| --- | --- |

![](/resources/Storage/clean-power-vfd-publication/res/acceleration-and-deceleration-times.jpg)