title: "Analog input loss (Code: 55, 56, and 57)"
id: "analog-input-loss"
project: "Clean Power VFD User Guide"
url: "https://smartd.clickhelp.co/articles/clean-power-vfd-publication/analog-input-loss"
updated: 2026-11-02T14:02:04Z
---

# Analog input loss \(Code: 55, 56, and 57\)

[Home](/articles/clean-power-vfd-publication/home) » [List and Details of alarms and protections](/articles/clean-power-vfd-publication/details-of-alarms-and-protections) » Analog input loss (Code: 55, 56, and 57)

* * *
 
This alarm applies to each of the 3 analog inputs that are configured.

**Trigger condition:**

This alarm arises if the analog input is configured for a 4..20 mA input signal and the current value falls under 3 mA for a duration longer than the triggering time delay

**Reset condition:**

The alarm resets when the signal returns to a value equal to or greater than 4mA for a duration longer than the user-defined reset delay.

**Delay on triggering:**

The time delay for alarm triggering is settable from 0.00s to 10.00s / default value = 0.15s

**Delay on reset:**

The time delay for alarm reset is settable from 0.00s to 10.00s / default value = 0.05s

## Reminder — Automatic Restart: 

If you want the drive to restart automatically when a **Medium** or **Major** fault/alarm clears itself, you must enable [Automatic Restart](/articles/clean-power-vfd-publication/automatic-restart). Otherwise, the drive stays stopped until you reset it and issue a new run command.