# Analog inputs setting

[Home](/articles/clean-power-vfd-publication/home) » [Functions and parameters](/articles/clean-power-vfd-publication/folder-functions-and-parameters) » [Inputs and outputs](/articles/clean-power-vfd-publication/i-o) » Analog inputs setting

* * *
 
The user can assign analog inputs. The options available are as follows:

* **[PTC sensor](/articles/clean-power-vfd-publication/motor-overheating-protection):** Reading from the PTC sensor connected to the analog input used for motor over-temperature alarm.
* **[Set motor frequency](/articles/clean-power-vfd-publication/motor-frequency-setpoint)**: Send a variable value to the VFD control to define the motor frequency setpoint.
* **[Set motor velocity](/articles/clean-power-vfd-publication/motor-velocity-setpoint)**: Send a variable value to the VFD control to define the motor velocity setpoint.
* For motor torque control:
    * **[Set motor torque](/articles/clean-power-vfd-publication/torque-setpoint):** Send a variable value to the VFD control to define the motor torque setpoint.
    * **[Set motor maximum torque](/articles/clean-power-vfd-publication/torque-setpoint-limits):** Send a variable value to the VFD control to define the maximum limit of the torque setpoint.
    * **[Set motor minimum torque](/articles/clean-power-vfd-publication/torque-setpoint-limits):** Send a variable value to the VFD control to define the minimum limit of the torque setpoint.
* If the PID is enabled in the configuration:
    * **[PID1 process feedback](/articles/clean-power-vfd-publication/pid-control-pv)**: Send the process value (PV) to the PID control.
    * **[PID1 setpoint](/articles/clean-power-vfd-publication/pid-control-setpoint)**: send the setpoint value (SV) to the PID control.
    * **[PID1 forced output value](/articles/clean-power-vfd-publication/pid-forced-output)**: Send a speed setpoint to the motor control when the PID forced output is activated and the source of the forced value is defined as an analog input.
* **Unspecified**

The user can also define the electrical signal connected to each analog input and scale it. The options available are as follows:

* **4 - 20 mA**: The input signal is a current between 4 and 20 mA.
* **0 - 10 V**: The input signal is a voltage between 0 and 10 V.
* **Resistor**: The input signal is a resistance from 500 to 10K Ohms.

![](/resources/Storage/clean-power-vfd-publication/analog%20io%20scaling_Scaling%20analog%20input.png)

**Example:**

A pressure sensor is connected to one of the analog inputs. It is used as the process feedback of a PID loop

This sensor delivers a 4 to 20 mA signal proportional to the detected pressure.

* Click on the I/O's configuration screen, click on the pen icon of the analog inputs to edit the configuration
* Then on the analog input, the sensor is wired to, i.e Ai1
* For the function, select Set PID#1 process feedback value (1)
* Mode: Select 4-20 mA (2)
* Then, on the scaling (3,) click on the values you need to edit and enter the number that fits the application.

![](/resources/Storage/clean-power-vfd-publication/Mob%20App%20ScreenShot%20Scale%20analog%20input.png)

![](/resources/Storage/clean-power-vfd-publication/analog%20io%20scaling_4%2020%20mA%20in%200%20to%2015%20psi.png)