# Analog inputs

**Analog inputs**

| Quantity |  | 3 analog inputs. Programmable |
| --- | --- | --- |
| Input types |  | 0..10VDC <br>4..20mA <br>0..24VDC <br>Impedance to read PTC temperature sensor <br>Default settings: 0..10VDC |
| Input impedances | 0..10VDC <br>4..20mA <br>0..24VDC<br><br>Impedance | &gt; 3.5k Ω <br>165 Ω <br>25 k Ω<br> <br>Supported external resistance range: 100 Ω to 100 kΩ.<br>The input circuit includes an internal protection resistance of approximately 50 Ω<br> <br>Do not let the output opened ( without load) when the selected type is 4 .. 20 mA |
| Insulation |  | None |
| Resolution |  | 12 bits |
| Time response |  | 50 ms |
| Accuracy |  | ± 1% at 25 °C (77 °F) / ± 2% for a temperature variation of 60 °C (108 °F) |
| Reference power supply for analog inputs |  | +10 VDC <br>Tolerance ± 2% for the temperature range of 20 °C to 30 °C. <br>Current: maximum 10 mA, short circuit protected. |