# Analog outputs setting

[Home](/articles/clean-power-vfd-publication/home) » [Functions and parameters](/articles/clean-power-vfd-publication/folder-functions-and-parameters) » [Inputs and outputs](/articles/clean-power-vfd-publication/i-o) » Analog outputs setting

* * *

The user can assign analog outputs. The options available are as follows:

* **Unspecified**: Not currently assigned to any specific task or function.
* **Motor frequency (Hz)**: The VFD outputs an electrical signal proportional to the motor frequency.
* **Motor current RMS (A)**: The VFD outputs an electrical signal proportional to the motor current RMS.
* **Motor velocity (RPM)**: The VFD outputs an electrical signal proportional to the motor velocity.
* **Active power (kW)**: The VFD outputs an electrical signal proportional to the motor’s actual power consumption.
* **Motor torque (%)**: The VFD outputs an electrical signal proportional to the motor torque in percentage

The user can also define the electrical signal connected to each analog output and scale it. The options available are as follows:

* **Unspecified**: There isn't any signal generated on the output
![](/resources/Storage/clean-power-vfd-publication/info.png) Do not keep the signal as "unspecified" when an analog output is assigned to one of the possible variables.
* **4 - 20 mA**: The output signal is a current between 4 and 20 mA.
* **0 - 10 V**: The output signal is a voltage between 0 and 10 V.

![](/resources/Storage/clean-power-vfd-publication/analog%20io%20scaling_Scaling%20analog%20output.png)

**Example:**

In this example, it is required to display the motor speed in Hz from a minimum operating speed of 30 Hz to a maximum of 120 Hz, thus onto a digital display meter with a 2 to 10 V input.

* Click on the I/O's configuration screen, click on the pen icon of the analog outputs to edit the configuration
* Then on the analog output, the digital display meter is wired to, i.e AQ1
* For the function, select Motor Frequency (Hz) (1)
* Mode: Select 0-10 (V) (2)
* Then on the scaling (3) click on the values you need to edit and enter the numbers that fits the application.

![](/resources/Storage/clean-power-vfd-publication/Mob%20App%20ScreenShot%20Scale%20analog%20output.png)

![](/resources/Storage/clean-power-vfd-publication/analog%20io%20scaling_30%20120%20Hz%20in%202%20to%2010V.png)