| Quantity |  | 2 analog outputs. Programmable |
| --- | --- | --- |
| Output types |  | 0..10VDC ( 20 mA max.) <br>0..20mA / 4..20mA |
| Output impedances | 0..10VDC <br>0..20mA / 4..20mA | 500 ohms minimum <br>75 ohms maximum |
| Isolation |  | None |
| Resolution |  | 12 bits |
| Response time |  | 50 ms (worst case from 0 to max output) |
| Accuracy |  | ± 1% at 25 °C (77 °F) / ± 2% for a temperature variation of 60 °C (108 °F) |