Analog outputs

Home » Technical Specifications » Control I/Os » Analog outputs 


Analog outputs

Quantity

  2 analog outputs. Programmable
Output types

 

0..10VDC ( 20 mA max.)
0..20mA / 4..20mA
Output impedances 0..10VDC
0..20mA / 4..20mA
500 ohms minimum
75 ohms maximum
Isolation

None
Resolution

 

12 bits
Response time

 

50 ms (worst case from 0 to max output)
Accuracy

 

± 1% at 25 °C (77 °F) / ± 2% for a temperature variation of 60 °C (108 °F)