# Check list: Before starting the Clean Power VFD

[Home](/articles/clean-power-vfd-publication/home) » Starting procedures » Check list: Before starting the Clean Power VFD

* * *
 
The following list intends to help the user go through a stepwise check before powering up the Clean Power VFD.

| Check | Item |
| --- | --- |
| ☐ | **Model number**.<br> <br>Check the model number of the Clean Power VFD to make sure you have received the correct model. |
| ☐ | **Environment.**<br> <br>Check that the area and environment around the Clean Power VFD comply with the specifications. |
| ☐ | **Power supply voltage.**<br> <br>Check that the power supply voltage is within the range of the input voltage specifications of the Clean Power VFD. |
| ☐ | **Motor voltage**<br> <br>Check that the nominal motor voltage corresponds to the output specifications of the Clean Power VFD. |
| ☐ | **Short-circuit protection**<br> <br>Check that a short-circuit protection is properly installed, complying with international and local regulations. |
| ☐ | **Power supply connections**<br> <br>Check that the main line power supply is correctly wired to the terminals R / L1, S / L2, and T / L3 of the Clean Power VFD. |
| ☐ | **Connection to the motor**<br> <br>Check that the Clean Power VFD is connected properly to the motor.<br> <br>The motor cables must correspond to the output terminals U / T1, V / T2, and W / T3 of the Clean Power VFD to respect the order of the phases.<br> <br>If the phase sequence is incorrect, the motor will rotate in the reverse direction. |
| ☐ | **Cross-section of the wires**<br> <br>Check that the cross-section of the wires complies with the recommendation of this document. |
| ☐ | **Voltage drop on the cable**<br> <br>Check that the voltage drop on the cable between the Clean Power VFD and the motor is less than 2% of the motor's nominal voltage. |
| ☐ | **Grounding**<br> <br>Check that the Clean Power VFD PE terminal is properly connected to the ground.<br> <br>Also: Check that the Motor ground wire is connected to the other Clean Power VFD PE terminal and NOT to the system ground |
| ☐ | **Power terminal screws tightening torque**<br> <br>Check that the power connectors' screws are tightened as specified in this document. |
| ☐ | **Power cable end connections**<br> <br>Check that the cables are not loosened from the terminals and not stripped too long, to avoid risks of short circuits. |
| ☐ | **Multiple motors protection**<br> <br>When using multiple motors on a single Clean Power VFD, ensure that each motor is installed with overload protection. |
| ☐ | **Cables for control**<br> <br>Check that all control wiring to the Clean Power VFD control circuit uses twisted pair cables. |
| ☐ | **Shielding**<br> <br>Check that all the shielding on all shielded cables is connected to the protective earth terminal.<br> <br>SmartD recommends using a copper earthing bar to do so. |
| ☐ | **Wiring preset**<br> <br>Check that the wiring preset (3-wires or 2-wires) complies with the schematic in this document. |
| ☐ | **STO1 and STO2 terminals**<br> <br>Check that the STO1 and STO2 terminals are correctly wired to a safety device. If STO is not used in your application, check that the STO1 and STO2 terminals are connected to the +24 terminal. |
| ☐ | **Control terminal screws tightening torque**<br> <br>Check that the screws on the control terminal blocks are tightened as specified in this document. |
| ☐ | **Control cables end connections**<br> <br>Check that the cables are not loosened from the control terminal blocks and not stripped too long, to avoid risks of short circuits. |
| ☐ | **Clean connection**<br> <br>Check that no cable copper strands touch other terminals or connections on the terminal block. |
| ☐ | **Foreign objects**<br> <br>Pick up any small pieces of cables or copper that may remain on or around the Clean Power VFD from your stripping and wiring operations. |
| ☐ | **Separation of power and control**<br> <br>Check that control circuit wires and main circuit wires (power supply and motor) are correctly separated. |
| ☐ | **Analog signals cables**<br> <br>Check that the cable for the analog signal is shorter than 30 m (98.4 ft). |
| ☐ | **STO cables**<br> <br>Check that the cable length for the STO signal, from operating contacts to the Clean Power VFD, is shorter than 30 m (98.4 ft) |