The following list intends to help the user go through a stepwise check before powering up the Clean Power VFD.
|
Check
|
Item
|
|---|---|
|
☐ |
Model number. Check the model number of the Clean Power VFD to make sure you have received the correct model. |
| ☐ |
Environment. Check that the area and environment around the Clean Power VFD comply with the specifications. |
|
☐
|
Power supply voltage. Check that the power supply voltage is within the range of the input voltage specifications of the Clean Power VFD. |
| ☐ |
Motor voltage Check that the nominal motor voltage corresponds to the output specifications of the Clean Power VFD. |
|
☐
|
Short-circuit protection Check that a short-circuit protection is properly installed, complying with international and local regulations. |
|
☐
|
Power supply connections Check that the main line power supply is correctly wired to the terminals R / L1, S / L2, and T / L3 of the Clean Power VFD. |
|
☐
|
Connection to the motor Check that the Clean Power VFD is connected properly to the motor. The motor cables must correspond to the output terminals U / T1, V / T2, and W / T3 of the Clean Power VFD to respect the order of the phases. If the phase sequence is incorrect, the motor will rotate in the reverse direction. |
|
☐
|
Cross-section of the wires Check that the cross-section of the wires complies with the recommendation of this document. |
|
☐
|
Voltage drop on the cable Check that the voltage drop on the cable between the Clean Power VFD and the motor is less than 2% of the motor's nominal voltage. |
|
☐
|
Grounding Check that the Clean Power VFD PE terminal is properly connected to the ground. Also: Check that the Motor ground wire is connected to the other Clean Power VFD PE terminal and NOT to the system ground |
|
☐
|
Power terminal screws tightening torque Check that the power connectors' screws are tightened as specified in this document. |
|
☐
|
Power cable end connections Check that the cables are not loosened from the terminals and not stripped too long, to avoid risks of short circuits. |
|
☐
|
Multiple motors protection When using multiple motors on a single Clean Power VFD, ensure that each motor is installed with overload protection. |
|
☐
|
Cables for control Check that all control wiring to the Clean Power VFD control circuit uses twisted pair cables. |
|
☐
|
Shielding Check that all the shielding on all shielded cables is connected to the protective earth terminal. SmartD recommends using a copper earthing bar to do so. |
|
☐
|
Wiring preset Check that the wiring preset (3-wires or 2-wires) complies with the schematic in this document. |
|
☐
|
STO1 and STO2 terminals Check that the STO1 and STO2 terminals are correctly wired to a safety device. If STO is not used in your application, check that the STO1 and STO2 terminals are connected to the +24 terminal. |
|
☐
|
Control terminal screws tightening torque Check that the screws on the control terminal blocks are tightened as specified in this document. |
|
☐
|
Control cables end connections Check that the cables are not loosened from the control terminal blocks and not stripped too long, to avoid risks of short circuits. |
|
☐
|
Clean connection Check that no cable copper strands touch other terminals or connections on the terminal block. |
|
☐
|
Foreign objects Pick up any small pieces of cables or copper that may remain on or around the Clean Power VFD from your stripping and wiring operations. |
|
☐
|
Separation of power and control Check that control circuit wires and main circuit wires (power supply and motor) are correctly separated. |
|
☐
|
Analog signals cables Check that the cable for the analog signal is shorter than 30 m (98.4 ft). |
|
☐
|
STO cables Check that the cable length for the STO signal, from operating contacts to the Clean Power VFD, is shorter than 30 m (98.4 ft) |