Check list: Before starting the Clean Power VFD

Home » Starting procedures » Check list: Before starting the Clean Power VFD 


The following list intends to help the user go through a stepwise check before powering up the Clean Power VFD.

Check
Item

☐

Model number.

Check the model number of the Clean Power VFD to make sure you have received the correct model.

☐

Environment.

Check that the area and environment around the Clean Power VFD comply with the specifications.

☐

Power supply voltage.

Check that the power supply voltage is within the range of the input voltage specifications of the Clean Power VFD.

☐

Motor voltage

Check that the nominal motor voltage corresponds to the output specifications of the Clean Power VFD.

☐

Short-circuit protection

Check that a short-circuit protection is properly installed, complying with international and local regulations.

☐

Power supply connections

Check that the main line power supply is correctly wired to the terminals R / L1, S / L2, and T / L3 of the Clean Power VFD.

☐

Connection to the motor

Check that the Clean Power VFD is connected properly to the motor.

The motor cables must correspond to the output terminals U / T1, V / T2, and W / T3 of the Clean Power VFD to respect the order of the phases.

If the phase sequence is incorrect, the motor will rotate in the reverse direction.

☐

Cross-section of the wires

Check that the cross-section of the wires complies with the recommendation of this document.

☐

Voltage drop on the cable

Check that the voltage drop on the cable between the Clean Power VFD and the motor is less than 2% of the motor's nominal voltage.

☐

Grounding

Check that the Clean Power VFD PE terminal is properly connected to the ground.

Also: Check that the Motor ground wire is connected to the other Clean Power VFD PE terminal and NOT to the system ground

☐

Power terminal screws tightening torque

Check that the power connectors' screws are tightened as specified in this document.

☐

Power cable end connections

Check that the cables are not loosened from the terminals and not stripped too long, to avoid risks of short circuits.

☐

Multiple motors protection

When using multiple motors on a single Clean Power VFD, ensure that each motor is installed with overload protection.

☐

Cables for control

Check that all control wiring to the Clean Power VFD control circuit uses twisted pair cables.

☐

Shielding

Check that all the shielding on all shielded cables is connected to the protective earth terminal.

SmartD recommends using a copper earthing bar to do so.

☐

Wiring preset

Check that the wiring preset (3-wires or 2-wires) complies with the schematic in this document.

☐

STO1 and STO2 terminals

Check that the STO1 and STO2 terminals are correctly wired to a safety device. If STO is not used in your application, check that the STO1 and STO2 terminals are connected to the +24 terminal.

☐

Control terminal screws tightening torque

Check that the screws on the control terminal blocks are tightened as specified in this document.

☐

Control cables end connections

Check that the cables are not loosened from the control terminal blocks and not stripped too long, to avoid risks of short circuits.

☐

Clean connection

Check that no cable copper strands touch other terminals or connections on the terminal block.

☐

Foreign objects

Pick up any small pieces of cables or copper that may remain on or around the Clean Power VFD from your stripping and wiring operations.

☐

Separation of power and control

Check that control circuit wires and main circuit wires (power supply and motor) are correctly separated.

☐

Analog signals cables

Check that the cable for the analog signal is shorter than 30 m (98.4 ft).

☐

STO cables

Check that the cable length for the STO signal, from operating contacts to the Clean Power VFD, is shorter than 30 m (98.4 ft)