# Clean Power VFDs Overview

[Home](/articles/clean-power-vfd-publication/home) » [How to select a VFD?](/articles/clean-power-vfd-publication/how-to-select-a-vfd) » Clean Power VFDs Overview

* * *
 
Values are given for the rated operating range of the Clean Power VFD ( -15 to 50°C without derating, 50 to 60℃ with derating of 2% per °C). If not specified otherwise (e.g., SDB-1-2220-AL)

## Sizes S3 - IP20 / UL type 1

| ![](/resources/Storage/clean-power-vfd-publication/frame%20S3%20front%20view_2.png) | **SDB-1-2110-A**<br> <br>Input voltage: 3~ 400 Y - 480 Y VAC<br> <br>Output current (ND): 22 A<br> <br>**SDB-1-2150-A**<br> <br>Input voltage: 3~ 400 Y - 480 Y VAC<br> <br>Output current (ND): 28 A<br> <br>**SDB-1-2185-A**<br> <br>Input voltage: 3~ 400 Y - 480 Y VAC<br> <br>Output current (ND): 34 A<br> <br>**SDB-1-2220-AL**<br> <br>Input voltage: 3~ 400 Y - 480 Y VA<br> <br>Output current (ND): 41 A @ 40 °C (104 °F) | **SDB-2-2150-A**<br> <br>Input voltage: 3~ 600Y/347Δ (\*)<br> <br>Output current (ND): 22 A<br> <br>**SDB-2-2185-A**<br> <br>Input voltage: 3~ 600Y/347Δ (\*)<br> <br>Output current (ND): 22 A<br> <br>**SDB-2-2220-A**<br> <br>Input voltage: 3~ 600Y/347Δ (\*)<br> <br>Output current (ND): 34 A |
| --- | --- | --- |

## Sizes S4 - IP20 / UL type 1

| ![](/resources/Storage/clean-power-vfd-publication/frame%20S4%20front%20view_2.png) | **SDB-1-2220-A**<br> <br>Input voltage: 3~ 400 Y - 480 Y VAC<br> <br>Output current (ND): 41A<br> <br>**SDB-1-2300-A**<br> <br>Input voltage: 3~ 400 Y - 480 Y VAC<br> <br>Output current (ND): 55A<br> <br>**SDB-1-2375-A**<br> <br>Input voltage: 3~ 400 Y - 480 Y VAC<br> <br>Output current (ND): 68A<br> <br>**SDB-1-2450-A**<br> <br>Input voltage: 3~ 400 Y - 480 Y VAC<br> <br>Output current (ND): 82A | **SDB-2-2300-A**<br> <br>Input voltage: 3~ 600Y/347Δ (\*)<br> <br>Output current (ND): 44A<br> <br>**SDB-2-2375-A**<br> <br>Input voltage: 3~ 600Y/347Δ (\*)<br> <br>Output current (ND): 54A<br> <br>**SDB-2-2450-A**<br> <br>Input voltage: 3~ 600Y/347Δ (\*)<br> <br>Output current (ND): 66A<br> <br>**SDB-2-2550-A**<br> <br>Input voltage: 3~ 600Y/347Δ (\*)<br> <br>Output current (ND): 79A |
| --- | --- | --- |

(\*): *600Y/347Δ identifies the certified electrical distribution system (600/347 V solidly grounded Wye supplied from a Delta-Wye transformer). It is not an indication that the Clean Power VFD is approved for direct connection to a 600 V Delta distribution system. Where the facility is supplied by a Delta system, an upstream transformer providing a solidly grounded Wye secondary is required.*