title: "Remote/ Local control source"
id: "control-source"
project: "Clean Power VFD User Guide"
url: "https://smartd.clickhelp.co/articles/clean-power-vfd-publication/control-source"
updated: 2026-10-30T19:41:13Z
---

# Remote/ Local control source

[Home](/articles/clean-power-vfd-publication/home) » [Functions and parameters](/articles/clean-power-vfd-publication/folder-functions-and-parameters) » Remote/ Local control source

* * *
 
![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Blue%20Notice.png)

In remote mode, you can not modify the configuration. To do so, you must switch to the local mode.

* * *

## Control Source

A Control Source determines who currently has the "steering wheel" to operate the Variable Frequency Drive (VFD). Even if multiple screens, apps, or automation systems are wired to the drive, only one source is allowed to control it at a time. Any commands coming from inactive sources are ignored.

## What the Sources Mean

* **Local :**Operating the drive directly in front of the machine. This includes:
    * The physical keypad/display on the VFD (the HMI).
    * A connected mobile app (the drive considers app commands identical to pressing buttons on the physical keypad).

 ****
* **Remote Source 1 & Remote Source 2:** External automated systems located away from the drive (such as a central PLC, a building automation network, or external hardwired pushbuttons).

* * *
![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Orange%20Warning.fr-CA.png)
**STOP COMMAND MAY BE INACTIVE**

Changing the control source can make a Start or Stop command from another source inactive.
In particular, when the digital inputs are configured for 3-wire control, a Stop pushbutton wired to a digital input does not stop the motor if the corresponding I/O control source is not the active control source.
For example, if Local control is active, pressing a Stop pushbutton connected to the remote digital inputs does not stop the motor.
Before operating the equipment or changing the control source, verify which Start and Stop controls are active.

Operational Stop commands are not safety functions. Use the appropriate emergency-stop, Safe Torque Off (STO), or energy-isolation function where required by the application.

* * *

## Behavior when changing the control source

Changing the control source while the motor is running does not automatically stop the motor.

### Switching from Local to Remote

If the VFD is running and the active control source is switched from **Local (HMI)** to **Remote (digital I/Os)** while using 3-wire control, the drive does not re-evaluate the current state of the digital inputs at the moment of the changeover.

As a consequence, a Run, Stop, or Direction state that is already present on a digital input may not be acted upon until a new valid 3-wire transition occurs, such as a new Start pulse or Stop action.

For example, the drive may continue running even though the remote Stop input is already in its active state when Remote control is selected. A new valid Stop transition is required.

### Switching from Remote to Local

If the VFD is running and the active control source is switched from **Remote (digital I/Os)** to **Local (HMI)**, the VFD keeps its current operating state until a new command is received from the Local control source.

Control authority moves to the HMI, but the drive may continue running with the last commanded Run/Stop/Direction state.

When Local control is active:

* Start, Stop, and Direction commands assigned to the remote digital inputs are no longer used to control the motor.
* A Stop pushbutton connected to a **3-wire Stop digital input does not stop the motor**.
* The motor must be stopped using a valid command from the Local control source or another applicable stopping function.

> 
> **IMPORTANT:** Switching to Local control does not place the VFD into a stopped state. Do not assume that an external wired Stop pushbutton remains active after switching from Remote to Local control.

### Recommendation

Avoid changing the active control source while the motor is running.

If a control-source change is required:

1. Bring the motor to a controlled stop using the currently active control source.
2. Change the control source.
3. Verify which Start and Stop controls are now active.
4. Issue a new Start command from the newly selected source when operation can safely resume.

## **Remote / Local**

Use **Remote control mode** when the VFD must be controlled remotely, for example:

* from a control room using digital and/or analog inputs;
* from a PLC;
* from a DCS;
* through a communication network.

In other words, the commands come from a system or an operator who is not located directly at the VFD.

Use **Local control mode** when the VFD must be controlled from its front-face HMI or locally through a connected SmartD mobile app, for example during commissioning, maintenance, or testing.

In Local mode, remote motor-control commands do not interfere with local operation.

In other words, an operator located close to the VFD has control of the motor.

![](/resources/Storage/clean-power-vfd-publication/res/local%20and%20remote%20control.png)

The switch between Local and Remote control modes can be performed:

* from the HMI;
* from the SmartD mobile app; or
* by using an assigned digital input.

## On the HMI

One of the icons below is displayed In the lower-right corner of the HMI to indicate the current control mode.

In **remote****control mode**: ![](/resources/Storage/clean-power-vfd-publication/remoteControl.png)

or in **local control mode**: ![](/resources/Storage/clean-power-vfd-publication/localControl.png)

If the remote control source is configured, you can switch between local and remote control by clicking on the icon.

**IMPORTANT:** When switching to Local control while the motor is running, the motor does not automatically stop. The HMI becomes the active control source. 
;Remote Start, Stop, and Direction commands, including a 3-wire Stop command assigned to a digital input, are no longer used to control the motor.

## On the mobile app

One of the icons below is displayed next to the VFD state:

In **remote control mode**: ![](/resources/Storage/clean-power-vfd-publication/remoteControl.png)

or in **local control mode**: ![](/resources/Storage/clean-power-vfd-publication/localControl.png)

If the mobile app is connected to the VFD, you could configure the VFD to be in local or remote control mode:

## Remote source selection

**![](/resources/Storage/clean-power-vfd-publication/Screenshot_App_SelectRemoteControls%20in%20Conf%20plan.jpg)**
![](/resources/Storage/clean-power-vfd-publication/Screenshot_App_opening%20remote%20control%20configuration.jpg)
The " Remote controls" section of the configuration wizard allows you to define

* the remote control sources;
* the selector used to switch between Local and Remote control; and
* the selector used to select the active Remote control source, when applicable.

## Source selection from the HMI

If the source selection is configured as HMI, regardless of the active control mode:

* The HMI can engage and disengage Remote control mode.
* The HMI can select Remote control source 1 or Remote control source 2 without restriction.
* A Remote control source cannot change the Remote/Local control mode or the active Remote control source.

![](/resources/Storage/clean-power-vfd-publication/Screenshot_App_Remote%20controls%20configuration%20screen.jpg)

## Source selection from Remote source 1 or 2

If the source selection is remote source 1 or 2 ( I/Os or Modbus/TCP):,

* If the VFD is in local control mode

    * HMI can change control mode and control source
* If the VFD is in remote control mode

    * HMI can engage remote control mode, but if it disengages it, the VFD will go to lockout because of “remote control override“
    * HMI cannot change the active remote control source
    * The source configured as the “source selection” can engage and disengage the remote control mode or remote control source (source 1 / 2) without restriction

![](/resources/Storage/clean-power-vfd-publication/Screenshot_App%20Remote%20control%20selection%20is%20remote%20source%201.jpg)
## Remote Control Scenarios
 
This section presents three common remote control configurations using discrete I/Os and explains how to set up the drive accordingly.
 
### Scenario 1: Remote Control Using Discrete I/O (Default Configuration)

In this configuration, we keep the **default Remote Control configuration**, where the **HMI is used to switch between Local and Remote modes**.
 
#### Wiring and Configuration​

| Terminal / Interface | Assigned Function | Typical Hardware Connected | Operating Behavior |
| --- | --- | --- | --- |
| Di3 | 3-wire Start | Normally Open (N.O.) momentary push-button | A momentary pulse starts the motor. The drive latches the run command internally. |
| Di4 | 3-wire Stop | Normally Closed (N.C.) momentary push-button | Circuit must remain closed for the drive to run. Opening the circuit clears the latch and stops the motor. |
| Di5 (Optional) | Frequency Select | Selector switch or PLC digital output | Toggles speed reference (e.g., switching between Ai1 and a pre-set speed). |
| Ai1 | Speed Reference | Potentiometer (0–10V) or PLC output (4–20mA) | Directly scales the output frequency between minimum and maximum limits. |
| HMI | Local / Remote Switch | Keypad LOC/REM button | Switches control authority between physical terminals and keypad buttons. |

#### Operation

1. Set the drive to **Remote mode** using the HMI.
2. Start and stop the motor using external push buttons connected to DI3 and DI4.
3. If **DI5 is OFF**, the drive uses **Analog Input 1** for the speed reference.
4. If **DI5 is ON**, the drive uses a **preset speed** defined in the parameter settings.
5. If you want the speed to be controlled **only** via analog input, do **not assign DI5**.

> 
> **IMPORTANT:** The 3-wire Start and Stop inputs are Remote control commands. They control the motor only when the corresponding Remote I/O control source is active.
> 
> If the drive is switched to **Local** control, pressing the Stop pushbutton connected to DI4 does **not** stop the motor. Use the HMI Stop command while Local control is active.

* * *

### Scenario 2: Remote Mode Controlled by a Digital Input
 
In this scenario, a digital input is used to toggle between Local and Remote modes. The **HMI is no longer used** for this function.
 
#### Wiring and Configuration

* **Digital Input 3**: 3-wire Start
* **Digital Input 4**: 3-wire Stop
* **Digital Input 5**: Frequency Select (optional)
* **Digital Input 6**: Control Mode (Remote/Local switch)
* **Analog Input 1**: Speed reference

| Terminal / Interface | Assigned Function | Typical Hardware Connected | Operating Behavior |
| --- | --- | --- | --- |
| Di3 | 3-wire Start | Normally Open (N.O.) momentary push-button | A momentary pulse starts the motor. The drive latches the run command internally. |
| Di4 | 3-wire Stop | Normally Closed (N.C.) momentary push-button | Circuit must remain closed for the drive to run. Opening the circuit clears the latch and stops the motor. |
| Di5 (Optional) | Frequency Select | Selector switch or PLC digital output | Toggles speed reference (e.g., switching between Ai1 and a pre-set speed). |
| Di6 | Remote/Local switch | Selector switch or PLC digital output | Switches control authority between physical terminals and keypad buttons. |
| Ai1 | Speed Reference | Potentiometer (0–10V) or PLC output (4–20mA) | Directly scales the output frequency between minimum and maximum limits. |

#### Operation

1. When **DI6 is ON**, the drive enters **Remote Control mode**.
2. When **DI6 is OFF**, the drive returns to **Local mode**.
3. HMI will display the **Remote mode status** when active.
4. Start/Stop behavior and speed selection (via DI5) remain as described in Scenario 1.

>  
> **IMPORTANT:**When DI6 switches the drive to Local control, the Start and Stop commands assigned to the Remote digital inputs are no longer active motor-control commands. In particular, the 3-wire Stop command on DI4 does not stop the motor while Local control is active.
>  

* * *

### Scenario 3: Remote Mode Controlled by Digital Input, with Selection Between I/Os and Network Control
 
In this configuration, we use one input to switch between **Local and Remote**, and another input to choose between **discrete I/O control** and **Network control**.
 
#### Wiring and Configuration

* **Digital Input 3**: 3-wire Start
* **Digital Input 4**: 3-wire Stop
* **Digital Input 5**: Control Source (I/O vs. Network)
* **Digital Input 6**: Control Mode (Remote/Local switch)
* **Analog Input 1**: Speed reference (used when in I/O mode)

| Terminal / Interface | Assigned Function | Typical Hardware Connected | Operating Behavior |
| --- | --- | --- | --- |
| Di3 | 3-wire Start | Normally Open (N.O.) momentary push-button | A momentary pulse starts the motor. The drive latches the run command internally. |
| Di4 | 3-wire Stop | Normally Closed (N.C.) momentary push-button | Circuit must remain closed for the drive to run. Opening the circuit clears the latch and stops the motor. |
| Di5 | Select remote control 1 / remote control 2 | Selector switch or PLC digital output | When remote source is active, select between remote control 1 (e.g discrete I/Os) and remote control 2 (e.g Modbus TCP) |
| Di6 | Remote/Local switch | Selector switch or PLC digital output | Switches control authority between remote control and Local. |
| Ai1 | Speed Reference | Potentiometer (0–10V) or PLC output (4–20mA) | Directly scales the output frequency between minimum and maximum limits. |

#### Operation

1. When **DI6 is ON**, the drive enters **Remote Control mode**. When OFF, it returns to **Local**.
2. When in Remote:

    * If **DI5 is OFF**, the drive is controlled via **discrete I/Os** (DI3/DI4 and Analog In 1).
    * If **DI5 is ON**, the drive switches to **Network control**.
3. The HMI will display that the drive is in **Remote mode** and indicate the active source (I/O or Network) depending on the state of DI5.

> 
> **IMPORTANT:** DI3 and DI4 control the motor only when the discrete I/O source is the active control source.
> 
> If **Local** control is selected, or if another Remote source such as network control is selected, the 3-wire Stop command assigned to DI4 does not stop the motor. Use a valid Stop command from the currently active control source.