# Relays setting

[Home](/articles/clean-power-vfd-publication/home) » [Functions and parameters](/articles/clean-power-vfd-publication/folder-functions-and-parameters) » [Inputs and outputs](/articles/clean-power-vfd-publication/i-o) » Relays setting

* * *
 
## Configuration:

You can configure a function to trigger a change in the relay's state (either energized or de-energized). The supported activation trigger functions are described below:

* **Not assigned**: No activation trigger, the relay is not used.
* **Ready-to-run**: When the power drive system (VFD + Motor) is ready to run, it waits for a Start command.
* **Motor running**: When the power drive system (VFD + Motor) is running.
* **Any alarm above minor**: When there is an active alarm (critical, major, or medium) on the VFD.
* **Motor lockout**: When the power drive system (VFD + Motor) is in the lockout state.
* **Motor torque:** When the VFD magnetizes the motor, it provides torque before ramping up.
* **Damper control:** When a command is sent to control the damper.
* **Active switchover limit**: Indicates which current limit is currently active via relay state.
* **Unacknowledged alarm:**when there is at least one unacknowledged critical, major or medium alarm

The user can also define the default coil state for each relay: Energized or De-energized.

## Relay's behavior when the activation trigger is ON:

* For relay R1 ( SPDT relay / Form C relay):
    * **Relay De-energized**: The NC contact of the relay is closed, and the NO contact of the relay is opened when the activation trigger is activated.
    * **Relay Energized**: The NO contact of the relay is closed and the NC contact of the relay is opened when the activation trigger is activated.
* For relays R2 and R3 (NO relay / Form A relay):
    * **Relay De-energized**: The contact of the relay is opened when the activation trigger is activated.
    * **Relay Energized:** The contact of the relay is closed when the activation trigger is activated.