**Digital outputs**

| Quantity |  | 3 |
| --- | --- | --- |
| Type |  | Relay |
| Relay 1 | Contact arrangement | SPDT (Form C) |
| NO contact features | Resistive load; AC:5A @ 250V; DC: 3A @ 30V |
| NC contact features | Resistive load; AC: 3A @ 250V; DC: 3A @ 30V |
| Protective Class | Class I |
| Relay 2 | Contact arrangement | SPST NO (Form A) |
| NO contact features | Resistive load; AC: 3A @ 250V; DC: 3A @ 30V |
| Protective Class | Class I |
| Relay 3 | Contact arrangement | SPST NO (Form A) |
| NO contact features | Resistive load; AC: 3A @ 250V; DC: 3A @ 30V |
| Protective Class | Class I |