# Installation position and distance

[Home](/articles/clean-power-vfd-publication/home) » [Installing the VFD](/articles/clean-power-vfd-publication/installing-the-vfd) » [Mechanical installation](/articles/clean-power-vfd-publication/mechanical-installation) » Installation position and distance

* * *
 
When selecting the installation location of the drive, check the following points:

* The Clean Power VFD must be installed on a surface that can support the weight of the device and is free from vibration exceeding the specified tolerances.
* The surface must be fire-resistant or flame-retardant and compliant with local electrical regulations.
* There must be sufficient clearance around the Clean Power VFD to allow air to circulate freely.

If the Clean Power VFD is installed inside an electrical panel, ensure that the cooling fan of the Clean Power VFD is properly located within the enclosure to ensure the proper evacuation of heat from both the Clean Power VFD and the enclosure.

### Mounting orientation

![](/resources/Storage/clean-power-vfd-publication/Mounting%20orientation.jpg)

For correct heat dissipation, the Clean Power VFD must be mounted vertically. But do not install it upside down.

Do not mount it on its side or on its back.