Home » Maintenance » Maintenance: Safety messages

- Maintenance and inspection can only be performed by skilled professionals.
Risk of personal injury.
- Maintain and inspect devices after power is off.
Risk of electric hazard.
- Repair or maintain the AC drive after a minimum of 5 minutes have passed since it is powered off.
This allows for the residual voltage in the capacitors to discharge to a safe value.
Failure to comply will result in personal injury.
- If you replace the Clean Power VFD with a new one, set and check the parameters again after the AC drive is replaced.
Failure to comply will result in personal injury.

- The VFD becomes hot during operation.
Avoid touching the VFD until it has cooled to avoid burns.

Lock out and tag out all potential energy sources before working on the Clean Power VFD.
Before inspecting the product, read all safety instructions in this manual.
Before you clean the product, ensure that the power is off.
Clean the Clean Power VFD with a dry cloth. Cleaning with wet cloths, water, solvents, or detergents may result in electric shock or damage to the product.
When a motor is used for the first time or when a motor is reused after being kept unused for a long time, or when a periodical inspection is performed, an insulation inspection shall be conducted, so as to avoid damaging the Clean Power VFD because of the insulation failure of the motor windings.
During the insulation inspection, the motor wires must be disconnected from the Clean Power VFD.
It is recommended to use a 500V mega meter, and the insulating resistance measured shall be 5MΩ.