# Modbus TCP

Modbus communication can be enabled or disabled using the Clean Power VFD mobile app.

When Modbus communication is disabled, the drive cannot receive remote control commands through Modbus. This prevents unintended operation initiated through Modbus but does not disable other control sources or replace required electrical safety procedures.

For configuration of local and remote control, see [Control source](/articles/clean-power-vfd-publication/control-source).

* **Communication speed:** Automatic.
* **MAC address:** Printed on the [product label](/articles/clean-power-vfd-publication/packaging/a/nqDkpbSS2XfHthQcmhl0hc).
* **Modbus application layer:** Standard.

![](/resources/Storage/clean-power-vfd-publication/info.png) **Device ID: MODBUS/TCP server accepts requests with slave ID=0x01**

**Parameters, Addresses, and Format**

Other clients/servers see the Clean Power VFD as a table of parameters.

This table can be downloaded as an Excel file, from the SmartD service website, on the [page network data files](https://services.smartd.co/network-parameter-data-files/)

**Registers MCx - Motor Control**

The registers MCx are dedicated to Motor Control

The command register MCC can be used to change the Clean Power VFD status from "Ready to run" to running.

The command register MCD can be used to run the motor in the forward or reverse direction.

The command register MCS can be used to read the motor status.

**Register SYSx - System State**

The registers SYSx are dedicated to the System State

The command register SYS can be used to read the system state

The command register SYSR can be used to reset the system after a[lockout](/articles/clean-power-vfd-publication/alarms-actions "Alarms actions (go to)").

**Registers ALxy - Alarms**

The registers ALxy are dedicated to alarms.

**Supported functions**

| Code | Function |
| --- | --- |
| 03 | Read holding registers. |
| 06 | Write a single register. |
| 16 | Write multiple registers |
| 23 | Read/Write multiple registers. |
| 43 | Read Device Identification |

**Note: Heartbeat Register**

The Heartbeat register is a communication integrity indicator between a PLC and a VFD within a MODBUS/TCP network.

Its primary purpose is to confirm an active and stable connection by requiring periodic polling.

The Clean Power VFD's Modbus socket will close with an inactivity of 30 seconds. To keep the TCP socket open, we recommend reading the Heartbeat register regularly, typically every 10 seconds.

If the Heartbeat register is not polled within the recommended time, the VFD will interpret the lack of response as a communication failure, triggering a MODBUS Communication Loss alarm.