title: "Motor cable, type, length, voltage drop, capacitance"
id: "motor-cable-length-and-voltage-drop"
project: "Clean Power VFD User Guide"
url: "https://smartd.clickhelp.co/articles/clean-power-vfd-publication/motor-cable-length-and-voltage-drop"
updated: 2026-10-29T18:46:32Z
---

# Motor cable, type, length, voltage drop, capacitance

[Home](/articles/clean-power-vfd-publication/home) » [Installing the VFD](/articles/clean-power-vfd-publication/installing-the-vfd) » [Electrical Installation](/articles/clean-power-vfd-publication/electrical-installation) » [Main electrical lines and motor connections](/articles/clean-power-vfd-publication/main-electrical-lines-and-motor-connections) » Motor cable, type, length, voltage drop, capacitance

* * *
 ![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Orange%20Warning.fr-CA.png)
Always verify that the selected wire gauge is compatible with the VFD’s terminal block specifications.

* * *

## Cable type

The Clean Power VFD produces a true sinusoidal output—much like a direct-on-line (DOL) supply—which significantly reduces electromagnetic stress, eliminates high-frequency switching noise, and allows very long motor cable runs without the need for output filters or special VFD-rated cables.

Standard industrial-grade power cables are suitable for most installations with the Clean Power VFD.

Unlike traditional PWM drives, our clean sine wave output typically allows you to avoid the cost and complexity of VFD-rated cables.

However, special cable types may still be considered for the following scenarios:
| Condition | Cable Type Recommendation | Rationale |
| --- | --- | --- |
| **&gt;300 m, shielded runs** | Use low-capacitance, shielded cable only if EMI/RFI mitigation is required | Shielding increases capacitance but provides physical/EMI protection in sensitive environments |
| **Parallel cable runs** | Use standard cable, properly sized and routed | To increase ampacity and reduce voltage drop without risk of reflection or imbalance |
| **Legacy motors** | Standard cable accepted; no special insulation needed | Clean sine wave avoids dV/dt stress; only voltage drop matters |

## Cable Length

The maximum length for the cable between the motor and the Clean Power VFD is **4,500 m (14,800 ft)**, thanks to its clean sine wave, which eliminates the need for output filters, even on extended runs, ensuring reliable motor operation in distributed installations.

However, the following considerations must be observed:

## Voltage Drop Consideration

Ensure that the voltage drop along the motor cable is properly accounted for during the installation process. If the calculated drop exceeds **3%** of the rated motor voltage, use a **larger conductor size** to minimize efficiency loss and torque degradation.

Voltage drop may be calculated using the following formula:

**Line loss voltage (V) = √3 x wire resistance (Ω /m) x wire length (m) x current (A)**

## Cable Capacitance Effects

While capacitance in cables is usually a concern for PWM drives, it still introduces **charging current** and reactive power flow even at 50/60 Hz.
 
* Longer or shielded cables have higher capacitance
* The charging current drawn by the cable adds to the total current at the source
* It can slightly distort the power factor and affect the voltage regulation on lightly loaded motors

**The impact is low** but noticeable for very long cables or light loads.

## Summary: Cable Length vs Cable Type
| **Cable Length** | **Cable Type Recommendation** |
| --- | --- |
| 0–150 m | Standard industrial cable. No filtering or shielding needed |
| 150–300 m | Standard industrial cable fits. In EMI-sensitive environments, use a VFD-rated cable if shielded |
| &gt;300 m | Standard industrial cable fits. For legacy motors or long shielded runs, consider a low-capacitance cable if shielded or parallel |
| &gt;1000 m | Requires impact analysis and validation. Check voltage drop, reactive current, and torque limits |

## Reminder

Clean sine wave output enables unmatched cable length freedom and motor compatibility. Still, proper cable sizing for voltage drop and current capacity remains essential for safe, efficient operation, especially for long runs or high-load motors.