---
title: "Mounting clearance distances and heat dissipation-VFDs size S3"
id: "mounting-clearance-distances-vfds-size-s3"
project: "Clean Power VFD User Guide"
url: "https://smartd.clickhelp.co/articles/clean-power-vfd-publication/mounting-clearance-distances-vfds-size-s3"
updated: 2026-10-29T18:46:22Z
---

# Mounting clearance distances and heat dissipation\-VFDs size S3

[Home](/articles/clean-power-vfd-publication/home) » [Installing the VFD](/articles/clean-power-vfd-publication/installing-the-vfd) » [Mechanical installation](/articles/clean-power-vfd-publication/mechanical-installation) » [Installation position and distance](/articles/clean-power-vfd-publication/installation-position-and-distance) » Mounting clearance distances and heat dissipation-VFDs size S3

* * *
 
**Minimum mounting clearance distances - single drive installation:**

![](/resources/Storage/clean-power-vfd-publication/Mounting-Clearance-and-air-flow-SDB12185A.jpg)

| Clean Power VFD models | A<br>mm / inch | B<br>mm / inch | C<br>mm / inch | D<br>mm / inch |
| --- | --- | --- | --- | --- |
| <ul><li>SDB-1-2110-A</li><li>SDB-1-2150-A</li><li>SDB-1-2185-A</li><li>SDB-1-2220-AL</li><li>SDB-2-2-220-A</li></ul> | 300 / 11.81 | 200 / 7.87 | 50 / 1.97 | 10 / 0.39 |

* * *

**Minimum mounting clearance distances - side-by-side drive installation:**

![](/resources/Storage/clean-power-vfd-publication/Clearance-and-air-flow-SDB12185A-side-by-side-mounting.jpg)

| VFD models | A<br>mm / inch | B<br>mm / inch | C<br>mm / inch | D<br>mm / inch | E<br>mm / inch |
| --- | --- | --- | --- | --- | --- |
| <ul><li>SDB-1-2110-A</li><li>SDB-1-2150-A</li><li>SDB-1-2185-A </li><li>SDB-1-2220-AL</li><li>SDB-2-2220-A</li></ul> | 300/11.81 | 200/7.87 | 50/1.97 | 10/0.39 | 50/1.97 |

If a VFD is mounted above another it is important to ensure that the air temperature around the upper unit is not heated beyond the specified maximum operating temperature by the exhaust from the lower unit.

An air guide between the VFDs is recommended to prevent the rising hot exhaust air from being drawn into the upper unit.

**Heat dissipation:**

| VFD models | W | BTU / h |
| --- | --- | --- |
| SDB-1-2110-A | 598 | 2040 |
| SDB-1-2150-A | 741 | 2530 |
| SDB-1-2185-A | 866 | 2955 |
| SDB-1-2220-AL | 990 | 3380 |

The heat dissipation values given in this section are based on the VFD driving a motor at its rated voltage, current, and frequency (rated load). At lower motor load, the actual heat dissipation is typically lower. Under overload or demanding operating conditions, it can be higher. Use these values as a reference for enclosure and cooling design.

**Airflow of fans:**

| VFD models | Fans | airflow | airflow |
| --- | --- | --- | --- |
| all VFD of S3 frame | 2 fans are located at the bottom of the VFD behind a metal screen | 212.6 CFM | 6.02 m3/min |