Mounting clearance distances and heat dissipation-VFDs size S4

Minimum mounting clearance distances - single drive installation:


Clean Power VFD models A
mm / inch
B
mm / inch
C
mm / inch
D
mm / inch
SDB-1-2220-A and SDB-2-2300-A 250 / 9.84 250 / 9.84 75 / 2.95 25 /0.98
SDB-1-2300-A and SDB-2-2375-A
250 / 9.84 250 / 9.84 75 / 2.95 25 /0.98
SDB-1-2375-A and SDB-2-2450-A
250 / 9.84 250 / 9.84 75 / 2.95
25 /0.98
SDB-1-2450-A and SDB-2-2550-A
250 / 9.84 250 / 9.84 75 / 2.95 25 /0.98 

Minimum mounting clearance distances - side-by-side drive installation:


VFD models A
mm / inch
B
mm / inch
C
mm / inch
D
mm / inch
E
mm / inch
SDB-1-2220-A and SDB-2-2300-A 250 / 9.84 250 / 9.84 75 / 2.95 25 /0.98 150 / 5.91
SDB-1-2300-A and SDB-2-2375-A
250 / 9.84 250 / 9.84 75 / 2.95 25 /0.98 150 / 5.91
SDB-1-2375-A and SDB-2-2450-A
250 / 9.84 250 / 9.84 75 / 2.95 25 /0.98 150 / 5.91
SDB-1-2450-A and SDB-2-2550-A
250 / 9.84 250 / 9.84 75 / 2.95 25 /0.98 150 / 5.91 

If a VFD is mounted above another it is important to ensure that the air temperature around the upper unit is not heated beyond the specified maximum operating temperature by the exhaust from the lower unit.

An air guide between the VFDs is recommended to prevent the rising hot exhaust air from being drawn into the upper unit.

Heat dissipation

VFD models W BTU / h
SDB-1-2220-A 1188 4050
SDB-1-2300-A
1611
5500
SDB-1-2375-A
2060
7030
SDB-1-2450-A
2693
9190

 The heat dissipation values given in this section are based on the VFD driving a motor at its rated voltage, current, and frequency (rated load). At lower motor load, the actual heat dissipation is typically lower. Under overload or demanding operating conditions, it can be higher. Use these values as a reference for enclosure and cooling design. 

VFD models W BTU / h
SDB-2-2300-A 2181
7442
SDB-2-2375-A
2467
8418
SDB-2-2450-A
3168
10809
SDB-2-2550-A
3607
12307

Airflow of fans

VFD models
Fans
airflow

SDB-1-2220-A and SDB-2-2300-A

SDB-1-2300-A and SDB-2-2375-A

SDB-1-2375-A and SDB-2-2450-A

SDB-1-2450-A and SDB-2-2550-A

2 fans are located at the bottom of the VFD behind a metal screen
560 CFM 15.9 m3/min