# Mounting instructions

[Home](/articles/clean-power-vfd-publication/home) » [Installing the VFD](/articles/clean-power-vfd-publication/installing-the-vfd) » [Mechanical installation](/articles/clean-power-vfd-publication/mechanical-installation) » Mounting instructions

* * *

Mount the Clean Power VFD inside a panel, on a pre-slotted plate, following the procedures provided hereafter.

Before installation, ensure that there is sufficient space to meet the clearance specifications and that there are no obstacles impeding the cooling airflow.

Select a wall or panel suitable to support the installation.

Refer to the[dimensions](/articles/clean-power-vfd-publication/dimensions "Dimensions (go to)") section in this document and check the Clean Power VFD's mounting bracket dimensions.

## 1- Prepare to mount with corresponding threaded holes

Use a level to draw a horizontal line on the mounting surface, and then carefully mark the fixing points.

Apply the mounting template (delivered with the Clean Power VFD) on the mounting surface to ensure the right position of the fixing points.

Distances are given in the mounting [dimensions](/articles/clean-power-vfd-publication/dimensions) section of this document

/resources/Storage/clean-power-vfd-publication/res/VFD_mounting_template.png

## 2- Drill and prepare fixtures

Drill the mounting bolt holes and then install the mounting bolts.

Fit screws and washers.

Do not fully tighten the bolts at this time.

## 3- Mount the Clean Power VFD

Mount the Clean Power VFD on the prepared mounting area via the keyhole suspensions.

Fully tighten the upper mounting bolts, then install two lower mounting bolts and tighten them fully to mount the VFD.

Ensure that the VFD is placed flat on the mounting surface and that the installation surface can securely support the weight of the VFD.

## 4- Clamping force of mounting screws

| ![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Blue%20Notice.png)<br>
<ul><li data-start="2185" data-end="2330">Always follow the <strong data-start="2218" data-end="2328">tightening torque recommended by the screw (fastener) manufacturer and by the support/anchor manufacturer.</strong></li> <li data-start="2185" data-end="2330">This manual specifies a <strong data-start="2440" data-end="2466">minimum clamping force</strong>, not a fixed tightening torque.<strong data-start="2218" data-end="2328"><br></strong></li> <li data-start="2185" data-end="2330">Ensure you use a flat washer to protect the VFD housing and a spring/lock washer (or thread-locking compound) to prevent loosening due to vibration.</li> <li data-start="2185" data-end="2330"><p data-start="85" data-end="125">SmartD Technologies Inc. is responsible for:</p> <ul data-start="127" data-end="340"> <li data-start="127" data-end="261"> <p data-start="129" data-end="261">Specifying the <strong data-start="144" data-end="164">mounting pattern</strong>, <strong data-start="166" data-end="192">permitted orientations</strong>, <strong data-start="194" data-end="204">weight</strong>, and <strong data-start="210" data-end="258">minimum recommended clamping force per screw</strong>.</p> </li> <li data-start="262" data-end="340"> <p data-start="264" data-end="340">Providing general installation guidelines for safe operation of the product.</p> </li> </ul> <p data-start="342" data-end="395">The <strong data-start="346" data-end="375">panel builder / installer</strong> is responsible for:</p> <ul data-start="397" data-end="905"> <li data-start="397" data-end="613"> <p data-start="399" data-end="613">Selecting a <strong data-start="411" data-end="438">suitable support system</strong> (material, thickness, reinforcement, anchors) that can safely carry the weight of the VFD and the specified clamping forces, including vibration and other mechanical loads.</p> </li> <li data-start="614" data-end="796"> <p data-start="616" data-end="796">Selecting <strong data-start="626" data-end="666">screws, anchors, and other fasteners</strong> compatible with the support material and following the <strong data-start="722" data-end="793">fastener/anchor manufacturer’s torque and installation instructions</strong>.</p> </li> <li data-start="797" data-end="905"> <p data-start="799" data-end="905">Ensuring that the final installation complies with <strong data-start="850" data-end="904">applicable codes, standards, and local regulations</strong>.</p> </li> </ul> <p data-start="907" data-end="1282">If the support deforms, cracks, or shows signs of damage during tightening, the installation is not acceptable.<br>The installer must <strong data-start="1038" data-end="1075">reinforce or redesign the support</strong> and adjust fastener selection and torque accordingly. <br>SmartD Technologies Inc. cannot be held responsible for damage or failure resulting from inadequate supports, incorrect fasteners, or improper installation.</p></li> </ul> |
| --- |

The tightening torque of the VFD mounting screws is **not fixed**.

It depends on several factors:
 
* The screw size (e.g. M6, M8)
* The screw material and property class (e.g. steel 8.8, stainless A2-70)
* The material and thickness of the support (sheet metal panel, concrete wall with anchors, etc.)

The mounting quality of the VFD does **not** depend directly on a specific tightening torque.
 
What really matters is the **clamping force** applied by the screws between the VFD and its support.
 
In real-world installations, the installer often does **not** know the exact characteristics of the support (material, thickness, type of anchors). For this reason, this manual does **not** specify a “one-size-fits-all” tightening torque. Instead, we specify a **minimum recommended clamping force** per mounting point.

You must choose:

* A suitable screw size and grade according the information given in the " dimensions" section of this document.
* A suitable **support and/or anchoring system**

and then apply a tightening torque (according to the fastener/anchor manufacturer) that achieves **at least this clamping force**, without damaging the support or the threads.

### Recommended clamping force
 
For correct mechanical fixation and to withstand vibration during operation, each mounting screw of the VFD should provide at least:

| VFD | Recommended clamping force per screw F |
| --- | --- |
| S3 frames VFD | 4893 N / 1100 lbf |
| --- | --- |
| S4 frames VFD | 9934 N / 2233 lbf |
| --- | --- |

### Support material and thickness
 
The clamping force specified in this manual assumes that the VFD is mounted on a **rigid, suitable support**.
 
The **choice of material, thickness, and anchoring system** for this support is part of the **panel / installation design** and is the responsibility of the installer or panel builder.
 
To ensure safe mounting:

* The support must be **mechanically strong enough** to carry the **weight of the VFD** plus a suitable safety margin and any dynamic loads (vibration, starting/stopping, shocks).
* The support must be **rigid enough** so that tightening the mounting screws to the required clamping force does **not cause permanent deformation** (bending, local buckling, tearing of thin sheet metal).
* The support must be **compatible with the chosen fasteners or anchors** (steel panel, mounting frame, concrete wall with anchors, etc.).

Typical examples of suitable supports include:

* Steel mounting plates or enclosure backplates designed for electrical equipment
* Rigid metal frames or mounting rails
* Concrete or masonry walls with correctly sized anchors (as per the anchor manufacturer’s instructions)

### How this ties back to clamping force and torque

1. The manual gives a **minimum clamping force per screw** (F).
2. The installer selects:

    * suitable support (material, thickness, type)
    * suitable fasteners / anchors for that support
3. The installer then:

    * uses the fastener/anchor manufacturer’s torque–tension data (or the approximate formula) to find the torque that produces at least F
    * checks that the support does not deform, and
    * adjusts the support design (reinforcement, different anchors, etc.) if necessary.

### From clamping force to tightening torque

This manual specifies a **minimum clamping force per mounting screw**instead of a fixed tightening torque.
 
To convert this clamping force into a tightening torque, proceed as follows:

1. Identify the screw size and grade

    * Example: M6 or M8, property class 8.8 steel.
2. Check the fastener or anchor manufacturer’s documentation

    * Look for a **torque–tension chart** (sometimes called “torque–preload” or “torque–clamp load” table). Example: [Fastenal+1](https://www.fastenal.com/content/feds/pdf/Torque-Tension%20Chart%20for%20A307%20Gr5%20Gr8%20Gr9.pdf?utm_source=chatgpt.com)
    * Find the row for your screw size and grade.
3. Select the torque that gives at least the specified clamping force

    * If the exact clamping force is not listed, choose the nearest higher value, without exceeding the manufacturer’s maximum recommended torque.
4. Set your torque wrench to that value and tighten all mounting screws evenly.

If the fastener manufacturer does not provide a table but only gives material properties, a qualified person may estimate the torque using the standard torque–tension relationship:

* **T** = tightening torque (in N·m)
* **F** = required clamping force (in kN)
* **d** = nominal screw diameter (in mm)
* **K** = “nut factor” (dimensionless), typically around **0.20** for clean, lightly lubricated steel metric screws, but this value can vary significantly with lubrication and surface condition.

* * *