# PID Control Process Value \(PV\)

[Home](/articles/clean-power-vfd-publication/home) » [Applications](/articles/clean-power-vfd-publication/applications) » [PID Control](/articles/clean-power-vfd-publication/pid-control) » PID Control Process Value (PV)

* * *
 
**![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Red%20Danger.png)**
 
**Loss of PID feedback can drive the motor to maximum output**
 
When PID control is active and the PID mode is set as **Direct**, a low feedback value can cause the VFD output to increase.
 
If the PID feedback uses a **0–10 V analog input**, a broken sensor, disconnected wire, or failed feedback signal can be interpreted as a valid 0 V value. In this condition, the PID controller can drive the motor to maximum speed or maximum output.
 
This can cause unexpected machine operation, overpressure, mechanical damage, process instability, serious injury, or death.
 
For PID feedback signals where loss of feedback could create a hazard, use a **4–20 mA feedback signal** with [analog input fault detection enabled](/articles/clean-power-vfd-publication/analog-input-loss), or use an external control system to detect sensor loss and bring the machine to a safe state.
 
Set the [Maximum PV alarm](/articles/clean-power-vfd-publication/pid-process-value-alarms) correctly to prevent the process variable from reaching a hazardous value. The Maximum PV alarm threshold must be set below the maximum safe process limit of the machine or installation.
 
Before operating the system, test the reaction to feedback sensor loss and verify that the machine remains within safe operating limits.
 
* * *

**1. The user must define the PID loop feedback input.**

The read value from the loop feedback is named the **Process Value** or **PV**

The choice can be made between an analog input or data from the communication media.

**2. The user must define the engineering units of his process.**

The VFD settings provide a list of usual engineering units, and It can be freely writable by the user (4 characters).

The list of engineering units is available in the section about [Control Parameters](/articles/clean-power-vfd-publication/pid-control-parameters/a/h2__462247566).

**3. The user must scale his process feedback value regarding the input variable scale of the loop feedback input:**

* Minimum input electrical signal (mA, V, Hexa or decimal value of the read data from the comm. …)
* Minimum input value within the engineering unit.
* Maximum input electrical signal (mA, V, Hexa or decimal value of the read data from the comm. …)
* Maximum input value within the engineering unit.

![](/resources/Storage/clean-power-vfd-publication/analog%20input%20scaling.svg)

**Example:**

PID loop feedback is a pressure transducer. Range 0 to 15 psi. Output 4 to 20mA, connected to Analog input 1.

Then the user setting must be as follows:

* PID loop feedback input is assigned to Analog input 1
* Analog input 1 is set as a 4 to 20 mA input
* Minimum input value= 0 psi
* Maximum input value= 15 psi

![](/resources/Storage/clean-power-vfd-publication/4%2020%20mA%20in%200%20to%2015%20psi.svg)