# PID forced output

[Home](/articles/clean-power-vfd-publication/home) » [Applications](/articles/clean-power-vfd-publication/applications) » [PID Control](/articles/clean-power-vfd-publication/pid-control) » PID forced output

* * *

The loop itself may require some maintenance. For example, to replace/clean a feedback sensor in the controlled process.

In some applications, this operation should not stop the process from running.

### Forced Output Command

A forced output command can be configured to force the output of the VFD to a speed output despite the loop being “broken“ during the maintenance operation.

The user can enable the forced output command. The forced output is "disabled" by default.

When the forced output command is enabled, the VFD output applies the forced output value.

### Forced Output Value

The forced output value can be configured between the minimum and maximum of the PID output values predefined by the user.

The forced output source could come from:

* a fixed preset value,
* an analog input,
* data from the communication network,
* or a variable written from the user interface (HMI or mobile App).

Its default value is " a fixed preset value"

Note that the analog input 1, 2, or 3 can be assigned to the forced output source during the I/Os configuration process.