# PID process value alarms \(Code: 46 and 47\)

[Home](/articles/clean-power-vfd-publication/home) » [List and Details of alarms and protections](/articles/clean-power-vfd-publication/details-of-alarms-and-protections) » PID process value alarms (Code: 46 and 47)

* * *

Depending on the application, users may need to set alarms on the feedback loop. These alarms help maintain control over the process and detect sensor issues.

## PID Low Process Value (PV) Alarm (Code: 46)

This is the minimum threshold for monitoring the process value.

Users can define it within the range of minimum and maximum input values (in user-defined engineering units).

The alarm can be enabled or disabled. By default, it is disabled.

The default threshold is the minimum input value.

When the Low PV alarm is triggered, the Variable Frequency Drive reacts based on the user's preset. Options include:

* Stopping the motor (coasting)
* Maintaining the current output speed: The VFD keeps the motor at the speed setpoint, which the PID controller set before the alarm.
* Forcing the output to a fixed user-preset value (refer to the Maintenance section for "forced output value")

The alarm reset threshold is 5% above the minimum process value alarm. 
Upon alarm reset, if the previous action was to stop the motor, the VFD returns to "ready to run" and awaits the run command. Otherwise, the VFD continues with PID control.

## PID High Process Value (PV) Alarm (Code: 47)

This is the maximum threshold for monitoring the process value.

Users can define it within the range of minimum and maximum input values (in user-defined engineering units).

The alarm can be enabled or disabled. By default, it is disabled.

The default threshold is the maximum input value.

When the High PV alarm is active, the VFD reacts according to the user's preset. The options are similar to those for the Low PV alarm.

The alarm reset threshold is 5% below the maximum process value alarm. Upon alarm reset, the VFD's behavior depends on the previous action, similar to the Low PV alarm.

## Delay

The corresponding alarm is triggered if the process value crosses an alarm threshold and stays there longer than the preset delay.

Users can set the Process Value Alarm Delay from 0 to 600 seconds. The default value is 10 seconds.

![Min and Max process value alarms](/resources/Storage/clean-power-vfd-publication/Window-alarm.png)

## Reminder — Automatic Restart: 

If you want the drive to restart automatically when a **Medium** or **Major** fault/alarm clears itself, you must enable [Automatic Restart](/articles/clean-power-vfd-publication/automatic-restart). Otherwise, the drive stays stopped until you reset it and issue a new run command.