---
title: "Power cables and fuses specifications for USA and Canada"
id: "power-cables-and-fuses-specifications-for-usa-and-canada"
project: "Clean Power VFD User Guide"
url: "https://smartd.clickhelp.co/articles/clean-power-vfd-publication/power-cables-and-fuses-specifications-for-usa-and-canada"
updated: 2026-11-05T21:29:27Z
---

# Power cables and fuses specifications for USA and Canada

[Home](/articles/clean-power-vfd-publication/home) » [Installing the VFD](/articles/clean-power-vfd-publication/installing-the-vfd) » [Electrical Installation](/articles/clean-power-vfd-publication/electrical-installation) » Power cables and fuses specifications for USA and Canada

* * *

## 
* [Fuse and cable selection](/articles/clean-power-vfd-publication/power-cables-and-fuses-specifications-for-usa-and-canada/a/h2_2026834259)
* [Using Circuit Breakers (“MCB/MCCB”) for Branch-Circuit Protection](/articles/clean-power-vfd-publication/power-cables-and-fuses-specifications-for-usa-and-canada/a/h2_1377322160)
* [What does “equivalent to fuse” mean here](/articles/clean-power-vfd-publication/power-cables-and-fuses-specifications-for-usa-and-canada/a/h2_1541134529)
* [Tested breaker part numbers (reference)](/articles/clean-power-vfd-publication/power-cables-and-fuses-specifications-for-usa-and-canada/a/h2__2080912726)
* [How to pick a breaker instead of a fuse (step-by-step)](/articles/clean-power-vfd-publication/power-cables-and-fuses-specifications-for-usa-and-canada/a/h2__1211757164)
* [Notes on terminology (to avoid confusion)](/articles/clean-power-vfd-publication/power-cables-and-fuses-specifications-for-usa-and-canada/a/h2__1747610926)
* [Keep the existing fuse/cable guidance](/articles/clean-power-vfd-publication/power-cables-and-fuses-specifications-for-usa-and-canada/a/h2__922239690)
* [UL-Certified Options by Model Group](/articles/clean-power-vfd-publication/power-cables-and-fuses-specifications-for-usa-and-canada/a/h2_341952096)

## Fuse and cable selection

The data listed in the table below are only used to select fuse and cable dimensions for the USA / Canada.

For power terminal wiring, use only 600 V 75℃ rated copper wire with the cable dimension specified in this document.

Verify if the chosen cable size can withstand the fault current (Iscc). Some cable manufacturers provide short-circuit current ratings for their cables.

Per UL 61800-5-1, branch-circuit protection is required by the NEC: Class J fuses (one per phase) or, where listed below, a UL 489 circuit breaker.

Fuses are not included in the purchased drive and must be provided by others.

Fuses with higher current ratings than the specified ones must not be used.

When installing a drive, always follow installation instructions and NEC requirements.

Refer to local codes and regulations.

| Clean Power VFD model | Recommended fuse | Cable for Power Connections | Cable for grounding connections |
| --- | --- | --- | --- |
| SDB-1-1750-A and SDB-2-2110-A | Class J, 25A , 600V | AWG 10 | AWG 10 |
| SDB-1-2110-A and SDB-2-2150-A | Class J, 30A, 600V | AWG 10 | AWG 10 |
| SDB-1-2150-A and SDB-2-2185-A | Class J, 40A, 600V | AWG 8 | AWG 8 |
| SDB-1-2-185 and SDB-1-2185-A | Class J, 50A, 600V | AWG 8 | AWG 8 |
| SDB-1-2220-A and SDB-1-2220-AL | Class J, 60A -600V | AWG 6 | AWG 6 |
| SDB-1-2300-A | Class J, 80A, 600V | AWG 4 | AWG 4 |
| SDB-1-2375-A | Class J, 90A, 600V | AWG 2 | AWG 2 |
| SDB-1-2450-A | Class J, 110A, 600VV | AWG 2 | AWG 2 |
| SDB-2-2220-A | Class J, 50 A, 600V | AWG 6 | AWG 6 |
| SDB-2-2300-A | Class J, 60A -600V | AWG 6 | AWG 6 |
| SDB-2-2375-A | Class J, 80A, 600V | AWG 4 | AWG 4 |
| SDB-2-2450-A | Class J, 90A , 600V | AWG 2 | AWG 2 |
| SDB-2-2550-A | Class J, 110A, 600V | AWG 2 | AWG 2 |

## Using Circuit Breakers (“MCB/MCCB”) for Branch-Circuit Protection

In the USA/Canada, branch-circuit protection must comply with **UL 489**/**CSA C22.2 No. 5** and **NEC** rules. In UL language, this device is a circuit breaker (often a molded-case circuit breaker, MCCB).

IEC “MCB” products (B/C/D curves) are not automatically equivalent unless they are UL 489 branch-circuit listed and meet the UL short-circuit conditions below.

## What does “equivalent to fuse” mean here

For each Clean Power VFD model family, UL testing establishes:

* a Short-Circuit Current Rating (SCCR) at a given system voltage, and
* The types and limits of protective devices (fuse class, breaker type, and their maximum ampere ratings) that may be used to achieve that SCCR.

If you use a circuit breaker instead of the listed Class J fuse, it must:

1. be **UL 489 branch-circuit listed**,
2. have an **interrupting rating ≥ the stated kA** at the stated voltage, and
3. **not exceed** the **maximum ampere rating** UL specifies for that VFD group.

> 
> If any of the three are not met, the installation **does not** achieve the stated SCCR.

## Tested breaker part numbers (reference)
 
Where SmartD lists tested breaker(s), use them to simplify selection (they meet the above UL conditions for the referenced models):

* HLL36070

>  
> You may use an **equivalent UL 489 breaker** from another brand **only if** it matches:
> 
> * the **kA interrupting rating at the same system voltage**,
> * the **instantaneous-trip characteristic if specified**, and
> * the **maximum ampere cap** stated above for that model group.
> 

## How to pick a breaker instead of a fuse (step-by-step)

1. **Identify your VFD model** and find its **UL SCCR group** above (100 kA or 50 kA, plus the allowed device type and maximum amperage).
2. **Confirm system voltage** (e.g., 480Y/277Δ V or 600Y/347Δ V) and match it to the breaker’s tested rating.
3. **Check the breaker’s interrupting rating (kAIC)** at that same voltage: it must be ≥ the UL SCCR stated for the VFD group.
4. **Check the breaker frame/ampere rating**: do not exceed the UL max A listed for that model group (e.g., ≤ 200 A in the 100 kA group; ≤ 70 A in the 50 kA group).
5. If the UL text calls for an instantaneous-trip type, the equivalent must have the same instantaneous behavior.
6. Apply all **NEC/CEC** rules for conductor sizing, terminals, ambient, and feeder/transformer SCC.

## Notes on terminology (to avoid confusion)

* **“MCB” (IEC)** vs **“MCCB/CB” (UL)**: In North America, UL/NEC branch-circuit protection uses UL 489 circuit breakers (often MCCB). An IEC MCB is not valid here unless it is UL 489 listed with adequate kAIC at the correct voltage and within the UL max amperage for the VFD group.
* **SCCR vs breaker kAIC**: The VFD SCCR is the level that the entire assembly can withstand when used with the specified protective device. Your breaker’s kAIC must meet or exceed that level at the same voltage.
* **“Max rating” in UL text**: This is a hard upper limit on the protective device’s ampere rating for that VFD group—do not exceed it, even if conductors would otherwise allow it.

## Keep the existing fuse/cable guidance
 
All cable rules you already state still apply (e.g., **600 V, 75 °C copper**, verify cable short-circuit withstand vs **Iscc**). Fuses remain fully valid: **Class J** with the specified **maximum ampere** and **voltage** per your model tables. Always follow **installation instructions**, **NEC/CEC**, and **local codes**.

SmartD recommends the device(s) that have been tested with the given Clean Power VFD model:

| Clean Power VFD model | Suitable circuit breaker |
| --- | --- |
| SDB-1-2185-A and SDB-2-2220-A | HLL36070 |

## UL-Certified Options by Model Group
 
#### A) High-fault rating — **SCCR = 100 kA**
 
**480 V class (up to 480Y/277 V or 480 V Δ)**
 
**Models:** SDB-1-2450-A, SDB-1-2375-A, SDB-1-2300-A, SDB-1-2220-A
 
**Use:** UL **Class J fuse**, **480 Vac**, **max 200 A**, **interrupting rating ≥ 100 kA**
 
**600 V class (up to 600Y/347 V or 600 V Δ)**
 
**Models:** SDB-2-2550-A, SDB-2-2450-A, SDB-2-2375-A, SDB-2-2300-A
 
**Use:** UL **Class J fuse**, **600 Vac**, **max 200 A**, **interrupting rating ≥ 100 kA**
 
B) High-fault rating — **SCCR = 50 kA**
 ![](/resources/Storage/clean-power-vfd-publication/warning.png) **For these models, you may select Class J fuses (≤ 100 A) or a breaker rated 50 kA at the correct voltage, provided it does not exceed 70 A.**

**480 V class (up to 480 Vac)**
 
**Models:** SDB-1-2185-A, SDB-1-1750-A, SDB-1-2110-A, SDB-1-2150-A, SDB-1-2220-AL
 
**Use:** UL **Class J fuse**, **480 Vac**, **max 100 A**, **interrupting rating ≥ 50 kA**
 
**600 V class (up to 600 Vac)\**

**Models:** SDB-2-2220-A, SDB-2-2110-A, SDB-2-2150-A, SDB-2-2185-A

**Use:** UL **Class J fuse**, **600 Vac**, **max 100 A**, **interrupting rating ≥ 50 kA**

Short-Circuit Current Ratings (SCCR) are valid only for the described configurations of VFDs with listed protections, using the specified UL Class J fuses.

SCCR is based on symmetrical RMS fault current at the stated system voltage; use of other protective devices or ratings may reduce the SCCR.