# Power Meter

[Home](/articles/clean-power-vfd-publication/home) » [Metrics](/articles/clean-power-vfd-publication/metrics) » Power Meter

* * *

![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Red%20Danger.png)

**ELECTRIC SHOCK HAZARD**

Do not use the Power Meter display to verify the absence of hazardous voltage.

A value of zero, a low displayed voltage, or the absence of a value on the HMI does not mean that the equipment is electrically safe to access.

Before installation, inspection, or maintenance work:

* Disconnect all power sources.
* Wait for the DC bus to discharge.
* Verify the status of the Power LED.
* Verify the absence of hazardous voltage using an appropriately rated measuring instrument and the required electrical safety procedure.

* * *

The **Power Meter** displays real-time electrical measurements of the Clean Power VFD, from the incoming power supply to the motor.

The screen is divided into three sections:

* **Line Meter** — measurements on the input side of the Clean Power VFD.
* **Motor Meter** — measurements on the output side of the Clean Power VFD, toward the motor.
* **DC Meter** — measurements of the internal DC bus.

The Power Meter is useful during commissioning, operation, maintenance, and troubleshooting to verify the electrical operating conditions of the drive and motor.

The values displayed in the Power Meter are live measurements. They continuously change according to the power supply, motor operating point, and mechanical load.

## Line Meter

The **Line Meter** displays the electrical measurements of the three-phase power supply connected to the Clean Power VFD.

| HMI display | Measurement | Description |
| --- | --- | --- |
| **I1** | Line current phase 1 | RMS current measured on input phase 1. |
| **I2** | Line current phase 2 | RMS current measured on input phase 2. |
| **I3** | Line current phase 3 | RMS current measured on input phase 3. |
| **V12** | Line-to-line voltage 1–2 | RMS voltage measured between input phases 1 and 2. |
| **V23** | Line-to-line voltage 2–3 | RMS voltage measured between input phases 2 and 3. |
| **V31** | Line-to-line voltage 3–1 | RMS voltage measured between input phases 3 and 1. |
| **f** | Line frequency | Measured frequency of the incoming power supply. |
| **PF** | Power factor | Ratio between active power and apparent power on the input side. |
| **P** | Active power | Electrical power actually transferred from or to the power supply. |
| **Q** | Reactive power | Reactive component of the electrical power. |
| **S** | Apparent power | Total apparent electrical power calculated from the voltage and current. |

The Line Meter can be used to identify abnormal supply conditions such as:

* Voltage imbalance between phases.
* Current imbalance.
* Incorrect line voltage.
* Incorrect or unstable supply frequency.
* Abnormally high input current.
* Unexpected power factor.

During commissioning, compare the measured values with the configured line parameters and the electrical installation specifications.

## Motor Meter

The **Motor Meter** displays the electrical measurements at the output of the Clean Power VFD.

| HMI display | Measurement | Description |
| --- | --- | --- |
| **Iu** | Motor current phase U | RMS current supplied to motor phase U. |
| **Iv** | Motor current phase V | RMS current supplied to motor phase V. |
| **Iw** | Motor current phase W | RMS current supplied to motor phase W. |
| **Vuv** | Motor voltage U–V | RMS voltage measured between motor output phases U and V. |
| **Vvw** | Motor voltage V–W | RMS voltage measured between motor output phases V and W. |
| **Vwu** | Motor voltage W–U | RMS voltage measured between motor output phases W and U. |
| **f** | Motor frequency | Electrical output frequency supplied to the motor. |
| **bal.** | Motor phase balance | Indicates the balance of the three motor phases. A value close to 100% indicates that the phases are well balanced. |
| **PF** | Motor power factor | Ratio between active power and apparent power on the motor side. |
| **P** | Active power | Electrical active power supplied to the motor. |
| **Q** | Reactive power | Reactive component of the motor electrical power. |
| **S** | Apparent power | Total apparent electrical power supplied to the motor. |

The Motor Meter can be used to observe how the motor responds to its operating point and mechanical load.

For example:

* Motor current normally increases as the required motor torque increases.
* Motor frequency follows the commanded operating frequency.
* Active power normally changes according to the mechanical load.
* Significant differences between the three phase currents may indicate an abnormal motor or wiring condition.

### Actual values versus configured values

The values displayed in the Motor Meter are **actual operating measurements**. They must not be confused with the motor nameplate parameters entered during configuration.

For example:

* **Motor nominal current** is the current specified on the motor nameplate.
* **Iu, Iv, and Iw** are the currents actually being supplied to the motor.

Similarly, the configured nominal motor voltage and frequency are reference values, while the Power Meter displays the values measured during operation.

## Understanding P, Q, S, and PF

The Power Meter displays the main electrical power quantities on both the line and motor sides.

**Active power (P)** is the portion of electrical power associated with useful energy transfer. It is expressed in watts or kilowatts.

**Reactive power (Q)** is the portion of power associated with the magnetic and electric fields of the electrical system. It is expressed in var or kvar.

**Apparent power (S)** represents the combined effect of active and reactive power. It is expressed in VA or kVA.

The relationship between these values is:

**S² = P² + Q²**

The **power factor (PF)** represents the ratio between active power and apparent power:

**PF = P / S**

A power factor close to **1.00** means that most of the apparent power is being transferred as active power.

## DC Meter

The **DC Meter** displays the voltage of the two sections of the internal DC bus.

| HMI display | Measurement | Description |
| --- | --- | --- |
| **−V** | Negative DC bus voltage | Voltage of the negative section of the DC bus relative to its internal midpoint. |
| **+V** | Positive DC bus voltage | Voltage of the positive section of the DC bus relative to its internal midpoint. |

The two values should normally remain reasonably balanced.

A significant difference between **−V** and **+V** may indicate an abnormal DC bus condition.

The total DC bus voltage corresponds approximately to the sum of the absolute values of the two measurements:

**DC bus voltage ≈ |−V| + |+V|**

For example, using the values shown in the Power Meter screen:

**367.5 V + 374.9 V ≈ 742.4 VDC**

The DC Meter is useful when investigating conditions related to:

* DC bus undervoltage.
* DC bus overvoltage.
* DC bus imbalance.
* Abnormal line supply conditions.
* Regenerative operation.
* Acceleration or deceleration behavior.

## Power flow and regenerative operation

During normal motoring operation, electrical energy flows:

**Power supply → Clean Power VFD → Motor**

The Clean Power VFD uses an **Active Front End (AFE)**. During regenerative operation, energy can flow in the opposite direction:

**Motor → Clean Power VFD → Power supply**

Power values may therefore change according to the operating condition of the motor and driven load.

## Using the Power Meter for troubleshooting

The Power Meter provides useful information when investigating abnormal operating conditions.

Examples include:

* Compare **V12, V23, and V31** when investigating line voltage imbalance.
* Compare **I1, I2, and I3** when investigating input current imbalance.
* Compare **Iu, Iv, and Iw** when investigating motor current imbalance.
* Check **f** on the Line Meter when investigating an abnormal supply frequency.
* Check the Motor Meter **f** value when confirming the actual output frequency.
* Check **P** when evaluating changes in motor load.
* Check **−V** and **+V** when investigating DC bus alarms.

The Power Meter should be used together with the alarm information and troubleshooting procedures provided in this User Guide.