# Powering the Clean Power VFD : Safety messages

[Home](/articles/clean-power-vfd-publication/home) » Starting procedures » Powering the Clean Power VFD : Safety messages

* * *

![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Orange%20Warning.fr-CA.png)

* When the Clean Power VFD is powered on, if there is an active command on the control inputs, the Clean Power VFD will run immediately.
* When using the 2-wire control method, ensure that the inputs are turned off before powering up the Clean Power VFD.

Risk of serious injury.

* Do not use a line-side contactor for routine motor control

When the Clean Power VFD is energized, the DC bus charges through an inrush-limiting circuit that is bypassed by an internal relay once charging is complete.

Using a magnetic contactor to switch input power on/off as a start/stop method is prohibited. Cyclic power switching (e.g., daily or repeated on/off) exposes the rectifier and inrush-limit components to repeated charging peaks, shortening their life and causing nuisance trips.

Required practice

* Use the contactor only for isolation, EPO (power removal), or section control—not for normal run/stop.
* Stop the drive first, then open the contactor. Do not open while the drive is decelerating a high-inertia or overhauling load.
* After opening, wait until the DC-bus discharges before re-closing. Implement a minimum OFF time and anti-reclose logic per product labeling.
* After closing, allow the drive to pre-charge and confirm “Ready/Healthy” before enabling any run command.

* * *

![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Yellow%20Caution.png)

* Resolve all faults before powering on the Clean Power VFD.

If a fault is still present when the Clean Power VFD is powered on, it will not exit the lockout state.

To remove the lockout state, follow the instructions from the [system reset](/articles/clean-power-vfd-publication/system-reset "System reset (go to)") chapter of this document.

* Quick pre-start checks: Verify that
* The input voltage is identical to the rated voltage of the product.
* The correct wiring of input terminals R, S, and T.
* The correct wiring of output terminals U, V, and W.

Risk of Clean Power VFD damage.