Powering the Clean Power VFD : Safety messages

Home » Starting procedures » Powering the Clean Power VFD : Safety messages 


  • When the Clean Power VFD is powered on, if there is an active command on the control inputs, the Clean Power VFD will run immediately.
  • When using the 2-wire control method, ensure that the inputs are turned off before powering up the Clean Power VFD.

Risk of serious injury.

  • Do not use a line-side contactor for routine motor control

When the Clean Power VFD is energized, the DC bus charges through an inrush-limiting circuit that is bypassed by an internal relay once charging is complete.

Using a magnetic contactor to switch input power on/off as a start/stop method is prohibited. Cyclic power switching (e.g., daily or repeated on/off) exposes the rectifier and inrush-limit components to repeated charging peaks, shortening their life and causing nuisance trips.

Required practice

  • Use the contactor only for isolation, EPO (power removal), or section control—not for normal run/stop.

  • Stop the drive first, then open the contactor. Do not open while the drive is decelerating a high-inertia or overhauling load.

  • After opening, wait until the DC-bus discharges before re-closing. Implement a minimum OFF time and anti-reclose logic per product labeling.

  • After closing, allow the drive to pre-charge and confirm “Ready/Healthy” before enabling any run command.


  • Resolve all faults before powering on the Clean Power VFD.

If a fault is still present when the Clean Power VFD is powered on, it will not exit the lockout state.

To remove the lockout state, follow the instructions from the system reset chapter of this document.

    • Quick pre-start checks: Verify that
    • The input voltage is identical to the rated voltage of the product.
    • The correct wiring of input terminals R, S, and T.
    • The correct wiring of output terminals U, V, and W.

    Risk of Clean Power VFD damage.