title: "Protection in regions following IEC"
id: "protection-for-iec"
project: "Clean Power VFD User Guide"
url: "https://smartd.clickhelp.co/articles/clean-power-vfd-publication/protection-for-iec"
updated: 2026-10-29T18:46:08Z
---

# Protection in regions following IEC

[Home](/articles/clean-power-vfd-publication/home) » [Installing the VFD](/articles/clean-power-vfd-publication/installing-the-vfd) » [Electrical Installation](/articles/clean-power-vfd-publication/electrical-installation) » Protection in regions following IEC

* * *

* [Tables of fuses](/articles/clean-power-vfd-publication/protection-for-iec/a/h2__1245202378)
* [Fuse Selection](/articles/clean-power-vfd-publication/protection-for-iec/a/h2_1301740534)
* [Choosing an upstream circuit breaker (IEC 60947-2)](/articles/clean-power-vfd-publication/protection-for-iec/a/h2_1644745764)

## Tables of fuses

| VFD Model | Rated input current<br><br>(A) | VFD's<br><br>Iscc (kA) | Fuse type gG | **Circuit Breaker (1)** |
| --- | --- | --- | --- | --- |
| SDB-1-2110-A, SDB-2-2150-A | 23 | 50 | 30A - 600V | GV3P25 |
| SDB-1-2150A, SDB-2-2185-A | 30 | 50 | 40A - 600V | GV3P32 |
| SDB-1-2185-A, SDB-2-2220-A | 36 | 50 | 50A - 600V | GV3P40 |
| SDB-1-2220-A, SDB-1-2220-AL | 43 | 50 | 63A - 600V | GV3P50 |
| SDB-1-2300-A | 58 | 100 | 80A - 600V | GV3P65 |
| SDB-1-2375-A | 71 | 100 | 100A - 600V | GV3P80 |
| SDB-1-2450-A | 86 | 100 | 125A - 600V | GV4L115 |
| SDB-2-2300-A | 47 | 100 | 63A - 600V | GV3P50 |
| SDB-2-2375-A | 57 | 100 | 80A - 600V | GV3P65 |
| SDB-2-2450-A | 69 | 100 | 100A - 600V | GV3P80 |
| SDB-2-2550-A | 83 | 100 | 125A - 600V | GV4P115N |

(1) *Breaker options are specified by the required protection level. They have not been type-tested by SmartD and must be verified for coordination by the installer/system integrator.*

## Fuse Selection

This section details how to select and size fuses upstream of a SmartD Clean Power VFD. Proper sizing protects the supply, feeder cables, and the drive's AFE/DC bus (against inrush and faults) while avoiding nuisance trips.

Key IEC references

* IEC 61800-5-1 Adjustable speed power drive systems — Safety requirements
* IEC 60269 Low-voltage fuses (gG/gL, aM, aR)
* IEC 60947-2 Low-voltage switchgear — Circuit-breakers
* IEC 60364 Low-voltage electrical installations (cables, ADS/disconnection, PE sizing)

**Inputs you need (from VFDs data):**

Collect these before sizing:

1. **Rated input current** of the selected Clean Power VFD at your line voltage.
2. **Prospective short-circuit current** at the drive line terminals.

*Tip:* SmartD’s multilevel SiC topology greatly reduces input harmonic current and inrush spikes compared to conventional drives, but you must still size upstream protection per IEC and our published ratings.

**Fuse types explained:**

gG: Provides full-range overload and short-circuit protection. It is commonly used as a feeder/branch device.

aR (Semiconductor Fuse): Offers the fastest limitation of I^2^t for short-circuit protection.

Warning: aR fuses are for short-circuit protection ONLY. They will not protect against overloads. If you select an aR fuse, you must coordinate it with a separate overload device (like an MCCB or electronic overload).

**gG fuse:**

Calculate the Gg fuse ratings based on standard IEC and industry guidelines for selecting fuse protection for VFDs. Here's how to determine the ratings:

Step-by-Step Calculation:

* Identify the rated input current of the VFD: Example: 36 A
* Apply the recommended IEC fuse sizing factor:

IEC and general industry practice typically recommend sizing a fuse between 125% to 150% of the VFD input current.

This factor ensures protection against short circuits and avoids nuisance trips during normal VFD operation and inrush currents.
* Check that the selected fuse has a breaking capacity ≥ Isc at the installation point (often 50…120 kA as marked on the fuse).

* Calculate preliminary fuse rating:

For example, at 36 A rated current: Minimum fuse size = 36 A × 1.25 = 45 A, and Maximum fuse size = 36 A × 1.50 = 54 A

* Select a commercially available fuse size (IEC Gg type) from standardized values:

IEC standard fuse sizes typically follow these increments:

16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160 A, etc.

From the calculated range (45–54 A), select the nearest standardized fuse size, typically rounding upwards:

In this example: 50 A.

**aR fuse:**

Select a fuse with In(aR) ≈ 1.25 × I of the Clean Power VFD (never below I)

If your plant has frequent brownouts/restarts or large bus capacitance banks, you may need up to ~1.6 × I to ride through pre-charge without nuisance fuse operation

Ensure fuse breaking capacity ≥ Isc (many aR are 80–120 kA at 400–500 V)

**Important:** aR fuses alone are NOT acceptable as the sole protective device (no overload protection). For fuse-only installations, use gG type. Add a close-coupled aR fuse in series with the gG only if:

* Enhanced semiconductor protection is required, AND
* You can demonstrate proper selective coordination between both fuses

## Choosing an upstream circuit breaker (IEC 60947-2)

**Thermal (overload) setting**: set I ≈ 1.05…1.2 × I.

**Instantaneous (magnetic) pickup**: VFDs need headroom for DC bus inrush. Adjustable-magnetic MCCBs: set **8…12 × I** as a typical starting point (tune to site behavior).

**Breaking capacity**: must be **≥ Isc** at the point of installation.

Instead of a thermal-magnetic breaker, you can use a **magnetic-only circuit breaker** (instantaneous trip only) upstream of a **Clean Power VFD** as the **short-circuit protective device (SCPD)**, but you must cover **overload** somewhere else (another upstream thermal device)