---
title: "Reset the Fan Operating Time value"
id: "reset-the-fan-operating-time-value"
project: "Clean Power VFD User Guide"
url: "https://smartd.clickhelp.co/articles/clean-power-vfd-publication/reset-the-fan-operating-time-value"
updated: 2026-10-29T18:46:17Z
---

# Reset the Fan Operating Time value

[Home](/articles/clean-power-vfd-publication/home) » [Maintenance](/articles/clean-power-vfd-publication/maintenance) » [Fan replacement](/articles/clean-power-vfd-publication/fan-replacement) » Reset the Fan Operating Time value

* * *

![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Blue%20Notice.png)

Do not reset the fan operating hours unless the corresponding cooling fans have been replaced. Resetting the counter without replacing the fans makes the recorded runtime inconsistent with the actual operating time of the installed fans.

* * *

The Clean Power VFD records the operating time of its cooling fans. Use the fan runtime information to monitor fan usage and to keep the maintenance information synchronized with the fans installed in the VFD.

The fan operating hours are retained by the VFD and can be viewed from:

* the HMI
* the Mobile App
* Modbus TCP

## View the fan operating hours

On the HMI, open **Fan details**.

The **Fan details** screen displays the following information for each fan:

| Field | Description |
| --- | --- |
| **#** | Fan number. |
| **Speed (rpm)** | Current fan rotational speed. |
| **Runtime (h)** | Accumulated operating time of the fan, in hours. |

Use the runtime value as maintenance information when evaluating or replacing the cooling fans.

The accumulated fan operating hours are also available through the Mobile App and Modbus TCP.

## Reset the fan operating hours

Reset the fan operating hours/articles/clean-power-vfd-publication/fan-replacementafter [replacing the cooling fans](/articles/clean-power-vfd-publication/fan-replacement). This starts the runtime counter again for the newly installed fans and ensures that the displayed operating time corresponds to the fans currently installed in the VFD.

To reset the fan runtime from the HMI:

1. Replace the cooling fan or fans according to the applicable fan replacement procedure.
2. Power the Clean Power VFD as required to access the HMI.
3. Open **Fan details**.
4. Select **Reset**.
5. Confirm the reset, if prompted.
6. Verify that the fan runtime has been reset.