# Routine inspections

[Home](/articles/clean-power-vfd-publication/home) » [Maintenance](/articles/clean-power-vfd-publication/maintenance) » Routine inspections

* * *
 
Regular checks of the following should be carried out to ensure the Clean Power VFD and installation reliability is maximized.

| Item | Inspection | Methods and tools | Expected results |
| --- | --- | --- | --- |
| Environment | Is the ambient temperature and humidity within the specifications range, and is there any dust, dirt, corrosive gas, oil mist, or foreign objects present? | Visual,<br><br>Thermometer,<br><br>Hygrometer,<br>Recorder | There must be no danger of freezing with an ambient temperature of -10 to 55˚C and no condensation with ambient humidity of less than 95%. |
| Enclosure door filters and fans | Check the airflow in the enclosure. | Visual<br><br>Replace or clean the filters if needed.<br><br>Replace the fans if needed. | Airflow from the enclosure door (in and out) is not obstructed. |
| Clean Power VFD overview | Is there any abnormal vibration or noise? | Visual and acoustic | No abnormality. |
| Power voltage | Are the input voltages within the specifications range? | Measure voltages between R/ S/ T (phase to phase) | Values are within the specifications range. |
| Cooling fan | Is there any abnormal vibration or noise? | Manual validation<br>Turn off the system and check the operation by rotating the fan manually. | The fan rotates smoothly. |
| HMI | Is the display value normal? | Visual<br>Check the displayed values and compare them with readings from external meters (voltmeter, ammeter, etc) | If there are variations, it should not be more than xx% |
| Motor mechanical health | Is there any abnormal vibration or noise? | Visual and acoustic | No abnormality. |