Routine inspections

Home » Maintenance » Routine inspections 


Regular checks of the following should be carried out to ensure the Clean Power VFD and installation reliability is maximized.

Item

Inspection

Methods and tools

Expected results

EnvironmentIs the ambient temperature and humidity within the specifications range, and is there any dust, dirt, corrosive gas, oil mist, or foreign objects present?

Visual,

Thermometer,

Hygrometer,

Recorder
There must be no danger of freezing with an ambient temperature of -10 to 55˚C and no condensation with ambient humidity of less than 95%.
Enclosure door filters and fansCheck the airflow in the enclosure.

Visual

Replace or clean the filters if needed.

Replace the fans if needed.

Airflow from the enclosure door (in and out) is not obstructed.
Clean Power VFD overviewIs there any abnormal vibration or noise?Visual and acousticNo abnormality.
Power voltageAre the input voltages within the specifications range?Measure voltages between R/ S/ T (phase to phase)Values are within the specifications range.
Cooling fanIs there any abnormal vibration or noise?

Manual validation

Turn off the system and check the operation by rotating the fan manually.
The fan rotates smoothly.
HMIIs the display value normal?

Visual

Check the displayed values and compare them with readings from external meters (voltmeter, ammeter, etc)
If there are variations, it should not be more than xx%
Motor mechanical healthIs there any abnormal vibration or noise?Visual and acousticNo abnormality.