# SDB\.\.\.\.A:  Power terminals specifications S3 and S4

[Home](/articles/clean-power-vfd-publication/home) » [Installing the VFD](/articles/clean-power-vfd-publication/installing-the-vfd) » [Electrical Installation](/articles/clean-power-vfd-publication/electrical-installation) » [Main electrical lines and motor connections](/articles/clean-power-vfd-publication/main-electrical-lines-and-motor-connections) » SDB....A: Power terminals specifications S3 and S4

* * *

## Power terminal specifications

The following specifications apply to S3 and S4 Clean Power VFD frames.
 
### Conductor selection
 
The supply and motor terminals accept solid and stranded conductors. A solid conductor consists of a single wire. A stranded conductor consists of several wires assembled into one conductor.
 
Select the conductor size and insulation temperature rating specified for your VFD model and installation. The maximum terminal connection capacity shown below does not determine the minimum conductor size required for the installation.

| Clean Power VFD frames | Terminal | Tightening torque | ![Stripping length for a stranded conductor](/resources/Storage/clean-power-vfd-publication/stripping%20length%20stranded%20wire%400.5x.png)![Stripping length for a solid conductor](/resources/Storage/clean-power-vfd-publication/stripping%20length%20solid%20wire%400.5x.png)Conductor stripping length | ![Conductor cross-section](/resources/Storage/clean-power-vfd-publication/Section%20of%20cable.png)Maximum conductor size |
| --- | --- | --- | --- | --- |
| S3 and S4 | Protective earth (PE / Ground) | -Rated: 3.8 N.m / 33.6 in-lbs<br> <br>-Recommended min: 3.73 N.m / 33.01 in-lbs<br> <br>-Recommended max: 4.5 N.m / 39.8 in-lbs | 18 mm<br> 0.71 in. | 35 mm^2^<br> 2 AWG |
| Supply<br> R/L1, S/L2, T/L3 | -Rated: 3.8 N.m / 33.6 in-lbs<br> <br>-Recommended min: 3.73 N.m / 33.01 in-lbs<br> <br>-Recommended max: 4.5 N.m / 39.8 in-lbs | 18 mm<br> 0.71 in. | Solid or stranded:<br> 35 mm^2^<br> 2 AWG |
| Motor<br> U/T1, V/T2, W/T3 |

### Conductor preparation and connection
 
1. Strip the conductor insulation to the length specified above, without damaging the conductor or cutting individual strands.
2. Insert the stripped conductor fully into the terminal. For stranded conductors, ensure that all strands enter the clamping area.
3. Ensure that insulation is not trapped in the clamping area.
4. Use a screwdriver that fits the screw head and tighten the terminal to the specified torque.

### Fine-stranded conductors and cable ends
 
Stranded conductors do not automatically require ferrules. Acceptance of stranded conductors does not mean that every fine-stranded cable, ferrule, or pin adapter is suitable.
 
Before using fine-stranded conductors, ferrules, or pin adapters, [contact SmartD](https://services.smartd.co/contact-support/) to confirm a termination suitable for your VFD model and applicable installation requirements, including UL requirements where applicable.