# Speed limits in torque control mode

[Home](/articles/clean-power-vfd-publication/home) » [Functions and parameters](/articles/clean-power-vfd-publication/folder-functions-and-parameters) » [Motor Control Mode](/articles/clean-power-vfd-publication/motor-control-mode) » [Motor torque (%)](/articles/clean-power-vfd-publication/motor-torque) » Speed limits in torque control mode

* * *

In torque control mode, the user must define the speed limits for which the motor should not exceed while attempting to reach the desired torque:

* Min Speed Limit in Torque Control Mode
* Max Speed Limit in Torque Control Mode

| ![Information](/resources/Storage/clean-power-vfd-publication/info.png) | These limits are different from the [motor min and max frequency](/articles/clean-power-vfd-publication/motor-min-and-max-frequency) in the motor parameters. However, the speed limits in torque control cannot exceed the max frequency as described in the parameter settings below. |
| --- | --- |

In torque control mode, the VFD is designed to maintain a constant torque, regardless of the speed of the motor. However, the speed limits set for the motor must also be respected for safety and longevity.

When the motor speed reaches either the high-speed or low-speed limit (measured by an encoder or estimated by the algorithm), the VFD adjusts its output to prevent the speed from exceeding that limit:

* If the speed reaches the high limit, the VFD stops increasing the supplied frequency while continuing to regulate torque as per the setpoint.
* If the speed reaches the low limit, the VFD stops decreasing the supplied frequency while still maintaining the torque setpoint.

This ensures the motor operates within safe speed boundaries without compromising torque control.

**Parameters setting:**

| Parameter | Setting range | Default value | Dependencies |
| --- | --- | --- | --- |
| Min Speed Limit in Torque Control Mode | -**rpm\_limit** to +**rpm\_limit** RPM<br><br>where rpm\_limit = max\_frequency\_hz \* nominal\_velocity\_rpm / nominal\_frequency\_hz | **-nominal\_velocity\_rpm** RPM<br>(signed as per counter-clockwise rotation direction) | This value can not be higher than the Max Speed limit defined by motor nameplate |
| Max Speed Limit in Torque Control Mode | -**rpm\_limit** to +**rpm\_limit** RPM<br><br>where rpm\_limit = max\_frequency\_hz \* nominal\_velocity\_rpm / nominal\_frequency\_hz | **+nominal\_velocity\_rpm** RPM<br>(signed as per clockwise rotation direction) | This value can not be lower than the minimum speed limit defined by motor nameplate |