title: "Spinning Direction Priority"
id: "spinning-direction-priority"
project: "Clean Power VFD User Guide"
url: "https://smartd.clickhelp.co/articles/clean-power-vfd-publication/spinning-direction-priority"
updated: 2026-10-29T18:46:02Z
---

# Spinning Direction Priority

[Home](/articles/clean-power-vfd-publication/home) » [Functions and parameters](/articles/clean-power-vfd-publication/folder-functions-and-parameters) » [Motor Control Mode](/articles/clean-power-vfd-publication/motor-control-mode) » [General](/articles/clean-power-vfd-publication/general)» [Spinning direction](/articles/clean-power-vfd-publication/spinning-direction) » Spinning Direction Priority

* * *

**Overview**

In forward and reverse motor operations applications, the **RUN FORWARD** and **RUN REVERSE** commands can be activated simultaneously.

The Spinning Direction Priority feature allows you to define how the Variable Frequency Drive responds in such scenarios.

This section explains the Spinning Direction Priority options and guides you through configuring the VFD to suit your application's needs.

**Purpose**

* **Prevent unintended motor behavior**when conflicting directional commands are received.
* **Provide flexibility**by allowing you to assign priority to either the forward or reverse command.
* **Enhance safety and control**by defining clear motor responses in simultaneous command situations.

**Spinning Direction Priority Options**

The VFD offers four configurable options when both **RUN FORWARD** and **RUN REVERSE** commands are received at the same time:

**1. Stop the Motor and Raise a Medium Alarm (Default)**

* **Behavior:**

The motor will **stop**according to the configured stop mode (e.g., ramp stop, coast stop).

* **Alarm:**

    A medium-level alarm is raised to indicate the simultaneous activation of conflicting commands.
* **Use Case:**

    This is best for applications requiring the motor to cease operation immediately upon detecting conflicting commands for safety or process reasons.

**2. Maintain Current State**

* **Behavior:**
    * If the motor is **stopped**or **freewheeling**, it will **not start**.
    * If the motor **runs**, it will **continue operating in its current direction**without change.
    * An event is recorded in the audit log of the occurrence of simultaneous commands.
* **Use Case:**

    Ideal for applications where unintended starts or changes in direction must be avoided unless explicitly commanded.

**3. Priority to RUN FORWARD**

* **Behavior:**

    * The motor will **start or continue running forward**, overriding any reverse command.
    * If the motor is running in reverse, it will **change direction to forward.**
* **Direction Change:**
It applies a [seamless direction change](/articles/clean-power-vfd-publication/change-spinning-direction) if it has been enabled and configured.
* **Use Case:**

    It is suitable when the forward operation is critical and should take precedence over reverse commands.

**4. Priority to RUN REVERSE**

* **Behavior:**

    * The motor will **start or continue running in reverse**, overriding any forward command.
    * If the motor is running forward, it will **change direction to reverse.**
* **Direction Change:**
It applies a [seamless direction change](/articles/clean-power-vfd-publication/change-spinning-direction) if it has been enabled and configured.
* **Use Case:**

    Ideal when the reverse operation is more critical and should override forward commands.

**Configuring Spinning Direction Priority**

In the advanced motor control settings, find the parameter labeled **"Spinning direction priority"**

Select the desired option based on your application requirements:

* **Stop the Motor and Raise a Medium Alarm (Default)**
* **Maintain Current State**
* **Priority to RUN FORWARD**
* **Priority to RUN REVERSE**

To ensure smooth direction changes without stopping the motor when the spinning priority is set to Forward or Reverse, follow these steps:

1. Go to **Advanced Motor Control Settings**.
2. Enable **[Seamless Direction Change](/articles/clean-power-vfd-publication/change-spinning-direction)**.

**![](/resources/Storage/clean-power-vfd-publication/res/Safety%20picture%20Yellow%20Caution.png)**

* **Review Application Requirements:** Before changing the spinning direction priority settings, assess the operational needs and safety implications.
* **Test Configurations:** After configuring, perform controlled tests to ensure the motor behaves as expected.
* **Consult Documentation:** For detailed information on alarms, stop modes, and the seamless direction change feature, refer to other sections of the user guide.

![](/resources/Storage/clean-power-vfd-publication/Control%20Diagrams_Priority%20of%20Spinning%20Direction_Priority%20of%20Spinning%20Direction.png)