# Torque Deactivation acceptance test

[Home](/articles/clean-power-vfd-publication/home) » [Maintenance](/articles/clean-power-vfd-publication/maintenance) » Torque Deactivation acceptance test

* * *
 
**Follow each step of the following procedure:**

**1- Stop the Clean Power VFD if it is running.**

Give a stop command.

Switch off the power input line.

Isolate the Clean Power VFD from the main line by a disconnector.

**RESULT:** The motor is stopped and is safely disconnected from power.

* * *

**2- Wait 5 minutes for the Clean Power VFD capacitors to be discharged.**

* * *

**3- Check that the Torque Deactivation circuit is correctly wired against the wiring diagram.**

* * *

**4- Check that proper cables are used and terminals are tightened with the recommended torque.**

* * *

**5- When previous steps have been checked and passed the verification, then switch on the disconnector to power up the Clean Power VFD.**

* * *

**6- Check the prevention to start**

Open the Torque Deactivation circuit.

Give a start command to verify that the Torque Deactivation function blocks the Clean Power VFD's operation.

**RESULT:** the drive displays a warning. The motor should not start.

* * *

**7- Reset and restart.**

Close the Torque Deactivation circuit.

Reset the Clean Power VFD status.

Give a start command.

**RESULT:** Check that the motor runs normally.

* * *

**8- Test during running.**

While the motor is running normally,

open one of the Torque Deactivation inputs.

**RESULT:** The motor should stop

Give a start command.

**RESULT: The motor must remain standstill.**

* * *

**9- Reset and restart.**

Close the Torque Deactivation circuit.

Reset the Clean Power VFD status.

Give a start command.

**RESULT: The motor runs**

* * *

**10- Test Torque Deactivation channel lost.**

Open one of the Torque Deactivation inputs.

**RESULT:** The motor stops and the alarm of the lost Torque Deactivation channel is raised

* * *

**11- Reset and restart**

Close the Torque Deactivation input.

Reset the Clean Power VFD status.

Give a start command.

**RESULT:** The motor runs normally.

* * *

**12- Test Torque Deactivation second channel lost.**

Open the other Torque Deactivation input.

**RESULT:** The motor stops and the alarm of the lost Torque Deactivation channel is raised

* * *

**13- Reset and restart.**

Close the Torque Deactivation input

Reset the Clean Power VFD status.

Give a start command.

**RESULT:** The motor runs normally.