Torque Deactivation acceptance test

Home » Maintenance » Torque Deactivation acceptance test 


Follow each step of the following procedure:


1- Stop the Clean Power VFD if it is running.

Give a stop command.

Switch off the power input line.

Isolate the Clean Power VFD from the main line by a disconnector.

RESULT: The motor is stopped and is safely disconnected from power.


2- Wait 5 minutes for the Clean Power VFD capacitors to be discharged.


3- Check that the Torque Deactivation circuit is correctly wired against the wiring diagram.


4- Check that proper cables are used and terminals are tightened with the recommended torque.


5- When previous steps have been checked and passed the verification, then switch on the disconnector to power up the Clean Power VFD.


6- Check the prevention to start

Open the Torque Deactivation circuit.

Give a start command to verify that the Torque Deactivation function blocks the Clean Power VFD's operation.

RESULT: the drive displays a warning. The motor should not start.


7- Reset and restart.

Close the Torque Deactivation circuit.

Reset the Clean Power VFD status.

Give a start command.

RESULT: Check that the motor runs normally.


8- Test during running.

While the motor is running normally,

open one of the Torque Deactivation inputs.

RESULT: The motor should stop

Give a start command.

RESULT: The motor must remain standstill.


9- Reset and restart.

Close the Torque Deactivation circuit.

Reset the Clean Power VFD status.

Give a start command.

RESULT: The motor runs


10- Test Torque Deactivation channel lost.

Open one of the Torque Deactivation inputs.

RESULT: The motor stops and the alarm of the lost Torque Deactivation channel is raised


11- Reset and restart

Close the Torque Deactivation input.

Reset the Clean Power VFD status.

Give a start command.

RESULT: The motor runs normally.


12- Test Torque Deactivation second channel lost.

Open the other Torque Deactivation input.

RESULT: The motor stops and the alarm of the lost Torque Deactivation channel is raised


13- Reset and restart.

Close the Torque Deactivation input

Reset the Clean Power VFD status.

Give a start command.

RESULT: The motor runs normally.