# Torque Deactivation inputs

[Home](/articles/clean-power-vfd-publication/home) » [Technical Specifications](/articles/clean-power-vfd-publication/technical-specifications) » [Control I/Os](/articles/clean-power-vfd-publication/control-i-os) » Torque Deactivation inputs

* * *

**Torque Deactivation inputs**

The torque deactivation inputs follow IEC 61131-2 type 1

| Quantity |  | 2 |
| --- | --- | --- |
| SIL capacity level | designed according to IEC61800-5-2 |  |
| Stop category |  | Category 0 |
| Torque Deactivation input reaction time |  | 20 ms |
| Torque Deactivation input filtering time |  | 5 ms |
| Nominal voltage of Torque Deactivation enabling input |  | 24 V |
| Maximum input voltage |  | 28.8 V |
| Logic threshold |  | 10V (+/- 5V) |
| Low state maximum voltage for disabling Torque |  | 5 V |
| Protective Class |  | Class I |