# Test run

[Home](/articles/clean-power-vfd-publication/home) » Starting procedures » Test run

* * *
 
###  Prerequisite

After the wiring checklist has been completed, follow the instructions below to test the Clean Power VFD.

This test procedure uses the digital and analog inputs of the Clean Power VFD to control it.

### Test run steps

1. **Unloaded motor**

Check that the motor is separated from its mechanical load.

1. **Turn on the power supply**

Turn on the power supply to the Clean Power VFD. Ensure that the HMI and LEDs are ON.

Switch on the breaker upstream of the Clean Power VFD.

If you power the control board via its 24VDC, switch it on to check its operation.

1. **Setting**

Use the mobile app to set the motor and Clean Power VFD parameters.

1. **Motor parameter**

Follow the wizard to set the motor parameter according to its nameplate.

1. **I/O's configuration**

Select the I/O's preset configuration complying with your wiring.

1. **Frequency reference**

Select the frequency reference as external from Analog input 1

1. **Acceleration and deceleration**

Set acceleration and deceleration times taking into account that this test runs an unloaded motor.

1. **Upload**

Follow the App instructions to upload the settings into the Clean Power VFD

1. **Press the run button**: Start the motor and check the motor rotates in the correct direction.

If the forward command is on, the 3 phases are wired in direct sequence, phases L1, L2, and L3 to the motor terminals U, V, and W in this order, the motor shall rotate in forward..

If the motor rotates in the reverse direction, stop the motor immediately.

You can change the default rotation direction via the setting parameter ["Phase Inversion"](/articles/clean-power-vfd-publication/motor-phase-reversal) without changing the wiring of the motor.

But if you prefer to exchange two phases on the output:

Then turn off the power supply to the Clean Power VFD.

Wait 5 minutes for the capacitors to discharge fully.

Finally, switch the cables at the U and V terminals.

Restart this test run from step 1.

1. **Change the speed**

Increase the analog input value slowly, then decrease it gradually.

The motor accelerates and decelerates accordingly to reach the speed set via the analog input

The set speed is displayed in the HMI

1. **Acceleration and deceleration**

Ensure that the motor accelerates and decelerates according to the set times and that the speed reaches the frequency reference.

Adjust acceleration and deceleration times.

Adjust torque boost parameters as described in the ["low-speed torque compensation"](/articles/clean-power-vfd-publication/starting-torque-boos) section.

and download your new settings if any.

1. **If you use the STO function**, test its operation:

Open STO1 / STO2 when the motor is running.

The motor should stop because the Clean Power VFD deactivates its output.

Try to start the motor while STO1 or STO2 is not activated. The motor should not start.

If they are not operating as expected, call SmartD technical support for assistance.