# Alarms Severity

[Home](/articles/clean-power-vfd-publication/home) » [Alarms and Protections](/articles/clean-power-vfd-publication/alarms-and-protections) » Alarms Severity

* * *

The Clean Power VFD manages its alarms on 4 levels of severity.

To catch the user's attention, the alarm displays different colors depending on the severity level.

| **Severity** | **Purpose** | **Default Action** |
| --- | --- | --- |
| **Minor** | A transitory fault with little impact on the drive and the process (such as a transient voltage drop). | The motor does not stop.<br><br>The fault is reset automatically when the cause disappears and does not need any acknowledgment. |
| **Medium** | The application can generate a fault or a non-destructive electrical fault ( such as a missing phase).<br>These are faults that may disappear without the need for human intervention. | The motor stops when the fault occurs and lasts longer than the filter timer if one is configured.<br><br>The user configures restart behavior during setup:<br><br>- Automatic restart, or<br><br>- Manual Restart with acknowledgment.<br><br>**Automatic Re-Start:**<br><br>The Clean Power VFD will attempt 4 times to detect whether the fault has been cleared, with each attempt separated by a time delay.<br><br>If the fault is still present, the drive elevates the event to a critical failure. If not, the drive restarts.<br><br>**Manual Re-Start with Acknowledge:**<br><br>The drive will restart only with a reset (acknowledgment) of the fault. To use this mode, the user must have configured the way to trigger the acknowledgment.<br><br>If the fault has been cleared, the drive goes into a ready-to-run state, and the motor can be re-started.<br><br>If the fault is still present, the drive goes to the standby position. |
| **Major** | This can be a fault from the drive or an external fault (such as a loss of a Torque Deactivation channel).<br><br>The generated fault could be destructive and/or dangerous to human beings.<br><br>This is an abnormal situation with imminent danger risk | Example: one Torque Deactivation channel is missing (mostly coming from a disconnected wire)<br><br>The user must analyze and fix the issue.<br><br>When fixed the VFD goes into the ready-to-run state, and the motor can be restarted. |
| **Critical** | This can be a fault from the drive or an external fault (such as a short circuit).<br><br>The generated fault can be immediately destructive.<br><br>This is a hazardous condition. | The fault cannot be reset automatically.<br><br><br><br><br><br>The user must identify and fix the issue.<br><br><br><br><br><br>The drive restarts if the fault is cleared, and after a full [reset from the user](/articles/clean-power-vfd-publication/system-reset) (a power off / power on cycle is the default reset operation for a critical fault). |

## Reminder — Automatic Restart: 

If you want the drive to restart automatically when a **Medium** or **Major** fault/alarm clears itself, you must enable [Automatic Restart](/articles/clean-power-vfd-publication/automatic-restart). Otherwise, the drive stays stopped until you reset it and issue a new run command.