Understand the Clean Power VFD part number

Home » Installing the VFD » Unboxing » Understand the Clean Power VFD part number 


The Clean Power VFD part number can be found on the identification label on the right side of the Clean Power VFD.

Please check that the model is suitable for the installation.


SD

B

-1

-2185

-A






Product Family

Smart Drive





Enclosure type:

B = UL type 1

F = Flange Mounting & UL type 1




Input Voltage in VAC:

1 = 3 ~ 400 to 480

2 = 3 ~ 600Y / 347Δ (*)



Motor Rating (1):

2110 = 22 A - 15HP / 11 kW 

2150 = 28 A - 20HP / 15 kW 

2185 = 34 A - 25HP / 18.5 kW 

2220 = 45 A - 30HP / 22 kW 

2300 = 55 A - 40HP / 30 kW 

2375 = 70 A - 50HP / 37 kW 

2450 = 85 A - 60HP / 45 kW 

2550 = 100 A - 75HP / 55 kW 

2750 = 130 A - 100HP / 75 kW 

2900 = 165 A - 125HP / 90 kW 

3110 = 165 A - 150HP / 110kW



VFD Type:

- = 6 pulses

-A = embedded AFE

-AL = embedded AFE + restricted operating temperature

 (*): 600Y/347Δ identifies the certified electrical distribution system (600/347 V solidly grounded Wye supplied from a Delta-Wye transformer). It is not an indication that the Clean Power VFD is approved for direct connection to a 600 V Delta distribution system. Where the facility is supplied by a Delta system, an upstream transformer providing a solidly grounded Wye secondary is required. 

(1): Motor power values are indicative. They vary depending on the motor type, technology, and manufacturer.The Clean Power VFD must not be selected from the motor power rating.The Clean Power VFD must be selected by skilled and experienced personnel.