title: "Wiring power connections"
id: "wiring-power-connections"
project: "Clean Power VFD User Guide"
url: "https://smartd.clickhelp.co/articles/clean-power-vfd-publication/wiring-power-connections"
updated: 2026-10-29T18:46:16Z
---

# Wiring power connections

[Home](/articles/clean-power-vfd-publication/home) » [Installing the VFD](/articles/clean-power-vfd-publication/installing-the-vfd) » [Electrical Installation](/articles/clean-power-vfd-publication/electrical-installation) » Wiring power connections

* * *

1. Wire your Clean Power VFD as per the [connection diagram](/articles/clean-power-vfd-publication/standard-connection-diagram).
2. **Select the appropriate cable** following the recommendation given in the section "Power cables and fuses specifications"

[For installation in the USA and Canada](/articles/clean-power-vfd-publication/power-cables-and-fuses-specifications-for-usa-and-canada)

/articles/clean-power-vfd-publication/power-cables-and-fuses-specifications-for-usa-and-canada[For installation in IEC regulation geographical area](/articles/clean-power-vfd-publication/protection-for-iec)

and connect the cable to one of the ground terminals of the Clean Power VFD.

![AFE VFD location of ground terminals](/resources/Storage/clean-power-vfd-publication/AFE%20VFD%20location%20ground%20terminals.jpg)

1. Carefully tighten the screw at the recommended torque. Torque values are listed [here](/articles/clean-power-vfd-publication/main-electrical-lines-and-motor-connections).
2. **Connect the other end of the ground cables** to the supply earth ground terminal.

Use a dedicated ground wire for input power, motor power, and control wiring.

Each Clean Power VFD must have its own low-impedance ground connection, ensuring that ground wires are as short as possible.

Do not daisy-chain ground connections between multiple Clean Power VFDs as shown in the diagram.

[![](/resources/Storage/clean-power-vfd-publication/res/Grounding%20Do%20and%20Dont.png)](/resources/Storage/clean-power-vfd-publication/res/grounding_Do_and_Dont.png "Click to enlarge")

1. **Locate the Clean Power VFD input and output terminals on the power terminal block**.

Refer to the detailed descriptions to understand the function and location of each terminal before making wiring connections.

1. **Connect the motor to the U/T1, V/T2, and W/T3 terminals.**

Run motor cable separately from other signals.

Follow the wiring requirements specified by the motor manufacturer.

1. **Connect the AC input power cables to R/L1, S/L2, and T/L3 terminals.**

****