Comprehensive Guide to Selecting Clean Power VFD and Motor

Home » How to select a VFD? » Comprehensive Guide to Selecting Clean Power VFD and Motor 


Choosing the right Clean Power Variable Frequency Drive (VFD) and motor for your application is essential for ensuring optimal performance, longevity, and system reliability.

Understanding the Application

Before selecting a Clean Power VFD and motor, it is crucial to understand the operating environment and the specific tasks to be performed. The selection process involves:

1. Motor Selection:

- Choose a motor based on the load's driving force and movement cycles.

- Basic movement cycle: start > acceleration > constant speed > deceleration > stop.

2. VFD Selection:

- Select a Clean Power VFD capable of driving the chosen motor effectively.

Key Considerations in VFD Selection

1. Motor Current Rating

The primary consideration when selecting a VFD is the motor's current rating.

The VFD must provide a current equal to or greater than the motor’s full load amperage (FLA). This ensures the motor can operate at its maximum capacity without the risk of underpowering.

Steps to Consider:

- Check the motor’s nameplate for its FLA.

- Ensure the VFD’s continuous current rating matches or exceeds this value.

2. Motor Operation Cycles

Understanding the motor’s operation cycles is crucial for choosing a VFD. This involves knowing how often the motor will start and stop, and the duration of these cycles.

Key Considerations:

- Frequent start/stop cycles can cause thermal stress.

- The VFD should be capable of handling the motor's duty cycle.

3. Motor Potential Temporary Overload

Motors often encounter temporary overload conditions that the VFD must handle without tripping.

Temporary Overload Capacity:

- VFDs are typically rated for overload conditions, such as 110% of the VFD’s rated current for 60 seconds.

- Ensure the VFD’s overload rating aligns with the motor’s overload rating in the application.

4. Ambient Temperature

The ambient temperature where the VFD operates significantly affects its performance and lifespan. Higher temperatures can reduce the VFD’s capacity and efficiency.

Temperature Adjustments:

- Check the VFD’s de-rating, which shows how current capacity decreases with rising ambient temperatures.

- Select a VFD with sufficient capacity to handle expected temperature ranges.

5. Duty Cycle ( IEC 60034 Definition)

The duty cycle, as defined by IEC standards, represents the ratio of operating time to rest time of the motor.

Duty Cycle Categories:

- Continuous operation (S1): Running at constant load for a long period.

- Short-time duty (S2): Running at a constant load for a limited time.

- Intermittent periodic duty (S3-S9): Cycles of running and stopping.

VFD Selection:

- Match the VFD to your motor application's specific duty cycle category.

- Ensure the VFD can handle the motor’s operating pattern.

6. Service Factor (NEMA Definition)

The service factor, as defined by NEMA, indicates the motor's ability to operate over its rated load under specific conditions.

Service Factor Implications:

- A motor with a service factor of 1.15 can operate at 115% of its rated load without damage.

- Select a VFD that can handle the motor’s rated load and service factor. This might mean choosing a VFD with a higher current capacity.

Additional Considerations for Specific Operations

1. Start

- The motor torque must be larger than the load starting torque.

2.  Acceleration

- The motor torque must be larger than the load torque required for acceleration:

- Motor torque > Load torque + Acceleration torque.

- Acceleration torque = (total inertia of the system * (target speed - starting speed)) / (9.55 * acceleration time).

3. Deceleration

- During deceleration, the motor acts as a generator, and energy flows back into the Clean Power VFD.

- The deceleration capability is determined by the Clean Power VFD's ability to consume or regenerate this energy.

- Ensure the deceleration time is correctly set to avoid triggering alarms or entering a "self-protective" lock state.

4. Constant Speed

- Check that the motor temperature rise specification is compatible with both the movement cycles and the operating environment.

- During acceleration or constant speed operation, the Clean Power VFD's capacity is limited by the peak current it can deliver to the motor.

- Ensure that the rated current output and overload capacity are the correct size for the application.

5. Clean Power VFD Current Ratings

Clean Power VFD current ratings are provided for Normal-duty operation = continuous operation (S1) / Running at constant load for a long period. It's an RMS value.

- It's the current rating suitable for variable torque applications where torque drops with speed. Overload capacity: 110% of the VFD nominal output current for 60 seconds every 10 minutes at 40°C.

6. Acceleration and Deceleration Time

When acceleration or deceleration time is restricted, the selection of the VFD cannot be based solely on matching the VFD current capacity with the motor's rated current.

Aggressive acceleration/deceleration rates will lead to higher currents, potentially causing overload or overcurrent faults. The system's capacity (VFD + motor) must be selected to satisfy the predetermined acceleration/deceleration time.

Ensure that the Clean Power VFD capacity is fully considered in advance for operations requiring frequent acceleration/deceleration, such as vertical lift operations.


Putting It All Together

1. Calculate the Required VFD Current Rating:

- Start with the motor’s FLA.

- Adjust for duty cycle and service factor.

- Consider potential overloads and ambient temperature.

2. Match the VFD Specifications:

- Verify that the chosen VFD meets or exceeds all calculated requirements.

- Ensure the VFD can handle the expected operational conditions.

Example Calculation:

- Motor FLA: 27 A

- Service Factor: 1.15

- Duty Cycle: S1 (Continuous)

- Potential Overload: 110% for 60 seconds

- Ambient Temperature: 40°C

Step-by-Step:

1. Adjust for Service Factor:

- Motor operational current = 27A x 1.15 = 31 A

2. Consider Overload Capacity:

- Overload current = 31 A x 1.1 = 34.1 A (for temporary conditions)

3. Temperature Adjustment:

- Check VFD de-rating: The Clean Power VFD has no derating up to 50°C

4. Choose a VFD:

- Select a VFD with a continuous current rating of at least 34 A, and ensure it supports the overload and duty cycle requirements.