The ratings are given for Normal Duty operation: Continuously available without overload.

The values are given for ambient temperature of 50 °C / 122 °F ( except: SDB-1-2185 and SDB-1-2220-AL: 40 °C / 104 °F ), at altitudes up to 2000m (6600 ft)

Apply the recommendation of the previous section to select the VFD that fits your application.

Rated Voltage Input  (VAC) 3~ 400 Y .. 480 Y –15%/+10% - Rated Frequency Input 50 and 60 Hz +/-5%


INPUTOUTPUT
Part Number

Input Current

(A)

Apparent
Power 
@ 480 VAC

(kVA)

Nominal

Output Current

(A)

SDB-1-2110-A
23
20
22
SDB-1-2150-A
30
25
28
SDB-1-2185
2924
34
SDB-1-2185-A
36
30
34
SDB-1-2220-AL
43
35.75
41 @ 40 °C (104 °F)
SDB-1-2220-A
43
35.75
41
SDB-1-2300-A
58
48.22
55
SDB-1-2375-A
71
50.03
68
SDB-1-2450-A
86
71.50
82

Rated Voltage Input (VAC) 3~ 600Y –15%/+10% - Rated Frequency Input 50 and 60 Hz +/-5% 


INPUT
OUTPUT
Part Number

Input Current

(A)

Apparent
Power 
@ 600 VAC

(kVA)

Nominal

Output Current

(A)

SDB-2-2150-A23
24
22
SDB-2-2185-A
30
32
28
SDB-2-2220-A
36
37.42
34
SDB-2-2300-A
47
48.84
44
SDB-2-2375-A
57
59.23
54
SDB-2-2450-A
69
71.7
66
SDB-2-2550-A
83
86.25
79