Digital inputs

Home » Technical Specifications » Control I/Os » Digital inputs 


Digital inputs

Digital inputs follow IEC 61131-2 type 1

Quantity
6 digital inputs named from DI1 to DI6.
Their assignment is settable by the user.
DI1 and DI2 can be assigned as encoder inputs. (1)
Note for SDB-1-2185: DI1 and DI2 can only be used for encoder
Input logic
Wire-able as Sink or Source logic, configurable by software.
Default: source.
Voltage levels in source mode ON 18 .. 24 V
OFF 0 .. 5V
Voltage levels in sink mode ON 0 .. 5V
OFF 18 .. 24 V
Current consumption
6 mA
Protective Class

Class I

Auxiliairy DC power output

Output power for digital inputs (2) +24VDC (-20% .. +20%) / 100 mA
Protective Class
Class I

(1) Clean Power VFD versions and compatibility with encoder:

Digital inputs 1 and 2 (Di1 and Di2) on the Clean Power VFD are compatible with pulse train signals with a maximum frequency of 50 kHz.

This compatibility applies to hardware produced on or after June 14, 2024.

You can verify this by checking the VFD's serial number. Ensure that the middle segment of the serial number is "20240614" or later (e.g., 0001-20240614-000001).

If your Clean Power VFD was manufactured before this date, it does not support the pulse train signal for the incremental encoder function.

(2) This auxiliary output power is protected against short circuits.