Home » Functions and parameters » Inputs and outputs » Relays setting
Configuration:
You can configure a function to trigger a change in the relay's state (either energized or de-energized). The supported activation trigger functions are described below:
- Not assigned: No activation trigger, the relay is not used.
- Ready-to-run: When the power drive system (VFD + Motor) is ready to run, it waits for a Start command.
- Motor running: When the power drive system (VFD + Motor) is running.
- Any alarm above minor: When there is an active alarm (critical, major, or medium) on the VFD.
- Motor lockout: When the power drive system (VFD + Motor) is in the lockout state.
- Motor torque: When the VFD magnetizes the motor, it provides torque before ramping up.
- Damper control: When a command is sent to control the damper.
- Active switchover limit: Indicates which current limit is currently active via relay state.
- Unacknowledged alarm: when there is at least one unacknowledged critical, major or medium alarm
The user can also define the default coil state for each relay: Energized or De-energized.
Relay's behavior when the activation trigger is ON:
- For relay R1 ( SPDT relay / Form C relay):
- Relay De-energized: The NC contact of the relay is closed, and the NO contact of the relay is opened when the activation trigger is activated.
- Relay Energized: The NO contact of the relay is closed and the NC contact of the relay is opened when the activation trigger is activated.
- For relays R2 and R3 (NO relay / Form A relay):
- Relay De-energized: The contact of the relay is opened when the activation trigger is activated.
- Relay Energized: The contact of the relay is closed when the activation trigger is activated.