Purpose
This feature allows the VFD to store up to two full configurations.
A configuration is a complete set of user settings used to operate the drive in a given application or setup. This can be useful when one VFD must support two different machine setups, two operating modes, or two motors that require different parameter sets.
At all times, only one configuration is active in the VFD.
What the function does
The VFD supports:
- 1 active configuration
- 1 inactive configuration
The active configuration is the one currently used by the VFD.
The inactive configuration is stored in memory and can be edited, saved, activated, or deleted, depending on the operating state of the drive.
The VFD cannot store more than two full configurations.
Default behavior
By default, the VFD contains:
- Configuration number 1 – Active
Only one valid active configuration is present after factory default or after reset to factory settings.
What is included in a configuration
A configuration stores a full set of application parameters, including for example:
- Command and reference settings
- Frequency or speed reference
- Torque or PID setpoint reference
- Acceleration and deceleration ramps
- Current limits
- Protection-related settings
- Motor control settings
- Application-specific parameters
The exact content depends on the features enabled in the VFD.
Access from HMI and Mobile App
You can manage configurations from:
- HMI
- Mobile app
You can:
- Edit the active configuration
- Save changes to the active configuration
- Save a second configuration
- Edit the inactive configuration
- Save and activate the inactive configuration.
- Delete the inactive configuration
- Activate the inactive configuration when the VFD is in the proper state
Save and activate
Save and activate stores the edited inactive configuration and immediately makes it the active configuration, if activation conditions are met.
When this happens:
- the previously active configuration becomes inactive
- the previously inactive configuration becomes active
Activating a configuration
The inactive configuration can only be activated when the VFD is in Ready to run state.
The inactive configuration can be activated by:
- HMI
- Mobile app
- Digital input
- Supported communication protocols
Activation behavior
If the selected configuration is inactive:
- the current active configuration becomes inactive
- the selected inactive configuration becomes active
If the selected configuration is already active:
- the VFD ignores the request
Deleting a configuration
Only the inactive configuration can be deleted.
The active configuration cannot be deleted.
After deletion, the VFD returns to a single valid active configuration.
Audit log
The VFD records the following actions in the audit log:
- save configuration
- activation of the inactive configuration
This helps track configuration changes over time.
Reset to factory
After a factory reset, the VFD returns to:
- one active configuration only
Any second stored configuration is removed.
Firmware upgrade and revert behavior
Upgrade from firmware with one-configuration support
When upgrading from an older firmware version that supports only one configuration, that existing configuration is kept and becomes:
- the default configuration
- the active configuration
Accept or commit of new firmware
When the new firmware is accepted or committed, the VFD supports for two configurations
Revert to firmware with one-configuration support
When reverting to an older firmware version that supports only one configuration, only one configuration is restored
Revert again to firmware with two-configuration support
When returning to a firmware version that supports two configurations, the two configurations are restored
Operating data and logs
Switching between configurations is intended to support different operating setups without losing stored application information.
Application-specific logs and operating data remain associated with their respective configuration or use case, according to system implementation.
Including:
- running hours
- start and stop history
- fault occurrences
- other operating records relevant to the application
Switching the active configuration does not erase the stored data associated with the inactive configuration.
When to use this function
Use this function when one VFD must support two distinct setups, such as:
- two different motors with different parameter requirements
- one machine with two operating modes
- one installation with a normal mode and an alternate mode
- commissioning and validated production configurations stored separately