Dual Configurations

Home » Functions and parameters » Dual Configurations 


Purpose

This feature allows the VFD to store up to two full configurations.

A configuration is a complete set of user settings used to operate the drive in a given application or setup. This can be useful when one VFD must support two different machine setups, two operating modes, or two motors that require different parameter sets.

At all times, only one configuration is active in the VFD.

What the function does

The VFD supports:

  • 1 active configuration
  • 1 inactive configuration

The active configuration is the one currently used by the VFD.

The inactive configuration is stored in memory and can be edited, saved, activated, or deleted, depending on the operating state of the drive.

The VFD cannot store more than two full configurations.

Default behavior

By default, the VFD contains:

  • Configuration number 1 – Active

Only one valid active configuration is present after factory default or after reset to factory settings.

What is included in a configuration

A configuration stores a full set of application parameters, including for example:

  • Command and reference settings
  • Frequency or speed reference
  • Torque or PID setpoint reference
  • Acceleration and deceleration ramps
  • Current limits
  • Protection-related settings
  • Motor control settings
  • Application-specific parameters

The exact content depends on the features enabled in the VFD.

Access from HMI and Mobile App

You can manage configurations from:

  • HMI
  • Mobile app

You can:

  • Edit the active configuration
  • Save changes to the active configuration
  • Save a second configuration
  • Edit the inactive configuration
  • Save and activate the inactive configuration. 
  • Delete the inactive configuration
  • Activate the inactive configuration when the VFD is in the proper state

Save and activate

Save and activate stores the edited inactive configuration and immediately makes it the active configuration, if activation conditions are met.

When this happens:

  • the previously active configuration becomes inactive
  • the previously inactive configuration becomes active

Activating a configuration

The inactive configuration can only be activated when the VFD is in Ready to run state.

The inactive configuration can be activated by:

  • HMI
  • Mobile app
  • Digital input
  • Supported communication protocols

Activation behavior

If the selected configuration is inactive:

  • the current active configuration becomes inactive
  • the selected inactive configuration becomes active

If the selected configuration is already active:

  • the VFD ignores the request

Deleting a configuration

Only the inactive configuration can be deleted.

The active configuration cannot be deleted.

After deletion, the VFD returns to a single valid active configuration.

Audit log

The VFD records the following actions in the audit log:

  • save configuration
  • activation of the inactive configuration

This helps track configuration changes over time.

Reset to factory

After a factory reset, the VFD returns to:

  • one active configuration only

Any second stored configuration is removed.

Firmware upgrade and revert behavior

Upgrade from firmware with one-configuration support

When upgrading from an older firmware version that supports only one configuration, that existing configuration is kept and becomes:

  • the default configuration
  • the active configuration

Accept or commit of new firmware

When the new firmware is accepted or committed, the VFD  supports for two configurations

Revert to firmware with one-configuration support

When reverting to an older firmware version that supports only one configuration, only one configuration is restored

Revert again to firmware with two-configuration support

When returning to a firmware version that supports two configurations, the two configurations are restored

Operating data and logs

Switching between configurations is intended to support different operating setups without losing stored application information.

Application-specific logs and operating data remain associated with their respective configuration or use case, according to system implementation.

Including:

  • running hours
  • start and stop history
  • fault occurrences
  • other operating records relevant to the application

Switching the active configuration does not erase the stored data associated with the inactive configuration.

When to use this function

Use this function when one VFD must support two distinct setups, such as:

  • two different motors with different parameter requirements
  • one machine with two operating modes
  • one installation with a normal mode and an alternate mode
  • commissioning and validated production configurations stored separately