Home » Clean Power VFD operation » Maintenance Mode
The Maintenance Mode allows users to temporarily disable specific motor-related alarms and place the Clean Power VFD into a maintenance state.
This mode is designed for troubleshooting, commissioning, or performing system maintenance without triggering nuisance alarms.
While in Maintenance Mode, the VFD remains operational and fully controllable by the user, but key motor protection features are deactivated.
- When to Use Maintenance Mode
- Key Effects of Maintenance Mode
- Enabling Maintenance Mode
- Disabling Maintenance Mode
- Audit Logging
When to Use Maintenance Mode
-
During motor maintenance or commissioning.
-
When performing system diagnostics.
-
To avoid false alarms during expected off-nominal motor behavior.
-
For temporary manual operation without fault interruption.
Key Effects of Maintenance Mode
When activated:
-
The VFD enters the Maintenance state.
-
The motor stops by using the normal ramp-down profile if it is running.
-
The following alarms are disabled:
-
Motor Current Balance
-
Motor Overcurrent
-
Motor Phase Loss
-
Motor Stalled
-
Motor Disconnected
-
Motor Wrong Direction
-
Encoder Speed Error
-
Encoder Communication Failure
-
Motor Overload
-
Motor Overspeed
-
Motor Underspeed
-
Motor Application Underload
-
Motor Ground Fault
-
-
The user retains full control of the VFD.
-
The VFD status is displayed as "Maintenance" on both the mobile app and the HMI.
If the forced value falls outside the user-defined process value limits, leading to a low or high process value condition, it indicates a configuration issue. As a result, the VFD will operate in degraded mode and trigger an alarm. The action taken by the alarm will depend on the following:
- Stop freewheeling: The motor will come to a halt.
- Forced value: Output the forced value (which is already in force).
- Keep actual speed: This action will not be executed.
Enabling Maintenance Mode
From HMI or Mobile App
-
Navigate to:
-
Menu > About > Diagnostic > Maintenance Mode
-
-
Toggle the Enable Maintenance Mode switch
-
A warning message will be displayed listing the deactivated alarms and potential risks
-
You must acknowledge and confirm to proceed
-
Once confirmed:
-
The VFD enters the OOS state
-
The top banner turns gold
-
VFD will stop (if running) and be ready for manual operation
-
From Remote Control Sources
You can also enable/disable Maintenance Mode via remote control, depending on your configuration:
-
Digital Input (if the remote control source is set to I/O)
-
Modbus TCP register (if source is Modbus)
-
BACnet IP object (if source is BACnet)
Consult your control system integration guide for the correct register/object mapping.
Disabling Maintenance Mode
To exit Maintenance Mode and return the VFD to normal operation:
-
Toggle Disable Maintenance Mode from the same menu or the remote interface
-
If the motor is running, the VFD will stop using the normal ramp-down profile
-
The VFD state will return to Ready to Run
-
All previously disabled alarms will be re-enabled
-
If PID was active, it will resume normal PID control
Audit Logging
Every enable/disable operation of Maintenance Mode is automatically recorded in the system Audit Logs for traceability and compliance.